El4132 - Technical Data - Beckhoff KL4132 Documentation

Dual-channel analog output terminal, -10 v to +10 v, 16 bit
Table of Contents

Advertisement

2.2

EL4132 - Technical data

Technical Data
Number of outputs
Power supply
Signal current
Load
Accuracy
Resolution
Electrical isolation
Conversion time
Current consumption from the K-bus
Bit width in the K-bus I/O
Configuration
Weight
Dimensions (W x H x D)
Mounting [} 11]
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative air humidity
Vibration / shock resistance
EMC immunity / emission
Protection class
Installation position
Approval
KL4132
KL4132
2
via the K-Bus
-10 V...+10 V
> 5 kΩ
< ±0.1 % (of the full scale value)
16 bits
500 V (K-Bus / signal voltage)
~ 1.5 ms
typically 75 mA
Output: 2 x 16 bits of data (2 x 8 bits control/status optional)
No address or configuration settings
approx. 85 g
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
0 °C to + 55 °C
-25 °C to +85 °C
95 %, no condensation
conforms to EN 60068-2-6 / EN 60068-2-27, see also Installation instructions for terminals
with enhanced mechanical load capacity [} 15]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus, ATEX [} 20]
Version: 3.0