Error Detection
Display
Error
Data transfer
error
Parameter
error
Resolver
disconnection
error
Operation
Status at time
mode
of error
PRG
RUN
Oper-
ating
∆ (see
×
note 2)
Note
1. Display:
Refers to the display on the Data Setting Console.
2. Operation mode:
Refers to the setting of the operation mode selector when the error occurs.
If there is a circle in both the PRG and RUN columns, it indicates that the
error applies to both modes. A triangle for the resolver disconnection error
indicates that the error applies only in PRG mode and when the power is
turned on.
Probable cause
Cam
output
The cam data is not set from
000 to 359 or 0FFF.
The data for setting the
number of revolutions
required for a single cycle is
outside of the allowable
range.
The decimal point position
data is other than 1, 2, or 4.
The numeric data is not in
BCD.
The memory upload and
memory download points
were turned ON
simultaneously.
The Data Setting Console
was operated during data
transmission.
Data transfer was executed
during Data Setting Console
operation.
The transfer bank number
was not from 1 to 8 or the
transfer cam number was not
1 to 48.
The transfer of the required
number of revolutions for a
single process (i.e., bank
selection) was executed
while the display on the Data
Setting Console was
flashing.
The DM m and DM m + 1 set
values are not correct. 0999
is exceeded in the general
DM area.
×
The resolver connection
cable is faulty.
Section 5
Possible correction
Clear the error (see
page 48), and then check
the probable causes
listed on the left. Correct
the problem and execute
the transfer again.
Correct the set values in
DM m and DM m + 1, and
then clear the error and
try again.
Replace the resolver
connection cable.
47