Commissioning (Basic Settings At Actuator); End Position Detection: Verify Setting; End Position Detection: Set Again Via Local Controls - AUMA SVM Series Operating Instructions Manual

Globe valve actuators with integral actuator controls
Table of Contents

Advertisement

SVM 05.1
SVM 07.5 / SVMR 05.1
Modbus RTU
10.

Commissioning (basic settings at actuator)

10.1.

End position detection: verify setting

10.2.

End position detection: set again via local controls

Information
SVMR 07.5
1.
Activate operation mode LOCAL:
If indication light [4] is blinking in blue: Operation mode LOCAL is
already active.
Indication light [4] is NOT blinking in blue: → Hold down push button
[2] for approx. 3 seconds until the indication light is blinking in blue.
The actuator can be operated using the push buttons [1
2.
Operate actuator using push buttons OPEN, STOP, CLOSE.
The end position detection is set correctly if (default indication):
-
the right indication light [3] is illuminated in yellow in end position CLOSED
-
the left indication light [1] is illuminated in green in end position OPEN
-
the indication lights go out after travelling into opposite direction.
The end position detection is set incorrectly, if:
-
the actuator comes to a standstill before reaching the end position
-
the left indication light is blinking in red
3.
If the end position setting is incorrect or not precise: <End position detection:
set again via local controls>.
Operation mode LOCAL must be activated for end position setting.
Activate operation mode LOCAL:
Hold down push button [2] for approx. 3 seconds until right indication light is
blinking in blue.
If the local controls are not provided on site, it is possible to connect an external
control module. The setting is then performed in the same way as described below.
Commissioning (basic settings at actuator)
3]:
33