Eiiiiiiiildd - ICP DAS USA I-7530 Series User Manual

Uart to can bus
Hide thumbs Also See for I-7530 Series:
Table of Contents

Advertisement

4.4 eIIIIIIIILDD...[CHK]<CR>
Description:
Transmit or receive expanded data frame
Syntax: eIIIIIIIILDD...[CHK]<CR>
e
IIIIIIII
L
DD...
Response:
Valid command: No response
Invalid command: ?<Error Code><CR>
Note:
In order to communicate with the computer to receive error information, the user
must enable the "Error Response" function in the CAN converter software.
Example:
Command: e1234567851122334455<CR>
Send a CAN message with an extended data frame. ID=12345678, DLC=5, data1=11,
data2=22, data3=33, data4=44 and data5=55.
I-7530, I-7530A, I-7565, I-7530-FT, tM-7530, tM-7530A, tM-7565 User Manual Version 1.6
Copyright © 2018 ICP DAS Co., Ltd. All Rights Reserved E-mail: service@icpdas.com
Stands for the extended (2.0B) data frame.
29 bits Identifier (00000000~1FFFFFFF)
Data length (0~8)
Input data frame value according to the data length (00~FF)