Pair Connection Mode: When the pair connection mode is selected, the setting
fields on the right will expand as below figure, and the order will be explained as
follows.
* Fixed CAN ID: Set a fixed CAN ID. Because in the CAN network, each CAN
converter must have a different CAN ID to avoid multiple converters with the same
CAN ID to send CAN messages to the CAN network at the same time, and the
messages of the same CAN ID to collide and cause errors. If the CAN specification
selected by the user is CAN 2.0A, the CAN ID is 11-bit ID, and the range is
000~7FF. If the CAN specification selected by the user is CAN 2.0B, the CAN ID is
29-bit ID, and the range is 00000000~1FFFFFFF.
* Response with CAN ID: The user can set whether to add the CAN ID before the
data and send to the UART side. The CAN ID is ASCII format, for example: CAN ID
is 001, when it is sent to the UART side and will display 0x30 0x30 0x31 as below
below.
I-7530, I-7530A, I-7565, I-7530-FT, tM-7530, tM-7530A, tM-7565 User Manual Version 1.6