Eiiiiiiiildd; Eiiiiiiiil[Chk]<Cr - ICP DAS USA I-7530A-MR-G User Manual

Rtu to can
Table of Contents

Advertisement

Send a CAN message with a standard remote frame. ID=2E8,
DLC=8.
eIIIIIIIILDD...[CHK]<CR>
4.3
Description: Send or receive an extended CAN data frame.
 Syntax: eIIIIIIIILDD...[CHK]<CR>
e
IIIIIIII
L
DD...
 Response: Valid command: No response
 Note: It is necessary to enable the "Error Response" function while using
the UART2CAN Utility in order to receive Syntax and/or communication
error information.
 Example:
Command: e1234567851122334455<CR>
Send a CAN message with an extended data frame. ID=12345678,
DLC=5, data1=11, data2=22, data3=33, data4=44 and data5=55.
EIIIIIIIIL[CHK]<CR>
4.4
Description: Send or receive an extended CAN remote frame.
 Syntax: EIIIIIIIIL[CHK]<CR>
E
IIIIIIII
L
 Response: Valid command: No response
 Note: It is necessary to enable the "Error Response" function while using
I-7530A-MR Modbus RTU to CAN Converter User's Manual (Version 1.08, 07/2019) ------------- 47
Stands for the extended (2.0B) data frame.
29 bits Identifier (00000000~1FFFFFFF)
Data length (0~8)
Input data frame value according to the data length (00~FF)
Invalid command: ?<Error Code><CR>
Stands for the extended (2.0B) CAN remote frame.
29 bits Identifier (00000000~1FFFFFFF)
Data length (0~8)
Invalid command: ?<Error Code><CR>

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-7530a-mr

Table of Contents