Forced Cooling Operation - Daikin FTX-N Series Service Manual

Inverter pair; wall mounted type
Hide thumbs Also See for FTX-N Series:
Table of Contents

Advertisement

Forced Cooling Operation

2. Forced Cooling Operation

Outline
The forced cooling operation is allowed when both the following conditions are met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Protection functions have priority over all other functions during forced cooling operation.
Procedure
 With the indoor unit ON/OFF button
 With the indoor unit's remote controller
(1) Press Mode button and select the cooling operation.
(2) Press On/Off button to turn on the system.
(3) Press Temp ,  buttons and Mode button at the same time.
(4) Press Temp ,  buttons, select " T ", and press Mode button for confirmation.
Indoor Unit
107
Press the indoor unit ON/OFF button for at least 5 seconds. (The operation will start.)
 Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press the indoor unit ON/OFF button.
 Forced cooling operation will stop automatically after about 30 minutes.
To stop the operation, press On/Off button.
Indoor unit ON/OFF button
Remote Controller
(R24540)
(1) (3) (4)
SiUS041638EA
(4)
(2)
(3) (4)
(R24541)
Trial Operation and Field Settings