Sia- Ifp-75 Panel Communicator - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Reporting
11.3 SIA– IFP-75 Panel Communicator:
(Differences/additional features are underlined).
The Events are sent to the Central Station Receiver as a fixed length string:
The Event Format is:
EEPPMMZZZZ
Where the Event Format is defined as follows:
Code
Event Code Description
Event code (2 characters)
EE
PP
Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM
Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically Module information)
ZZZZ
Event parameter (4 digits – Zero Filled) (typically Point, Zone or Circuit information)
1.
The Event field will contain 10 digits including the 2 digit Event Code (EE), 2 digit panel ID (PP), 2 digit Module Number (MM) and a
4 digit Event Parameter (ZZZZ).
2.
Based on the actual Event Code, the Module Number or Event Parameter fields might not contain pertinent information. In that case the
field will contain zeros.
3.
The account number is sent using an account block that is separate from the event block.
4.
Multiple events can be sent within a single event block. Events are separated by a "/" character.
5.
Event parameter can be a Zone, Point or Circuit Number.
6.
"pi" modifier event is not used.
7.
Panel can be set to report by either Point or Zone.
For examples, see Table 11.4.
Event
Fire Alarm-Zone
Fire Alarm-Zone
Fire Alarm-Point
Fire Alarm-Point
Expander Trouble
Auto Test
Battery Trouble-Panel 32
Battery Trouble-Expander 18 n/a
SLC Loop Shorted
Program Begin
Program Begin
AC Power Loss- Panel 22
Fire Trouble
Fire Trouble
Fire Trouble-NAC
Fire Trouble-NAC
126
Report
Panel ID
Module
Zone/Point
PP
MM
Zone
32
n/a
Zone
32
n/a
Point
32
01
Point
21
33
n/a
15
11
n/a
32
n/a
n/a
32
98
32
18
n/a
01
44
n/a
32
n/a
n/a
22
n/a
n/a
22
98
Point
22
97
Zone
22
97
Point
22
98
Zone
22
98
Table 11.4 SIA Reporting Examples
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Zone
Point
ZZZZ
ZZZZ
15
n/a
EE-PP-MM-ZZZZ
05
n/a
EE-PP-MM-ZZZZ
n/a
123
EE-PP-MM-ZZZZ
n/a
203
EE-PP-MM-ZZZZ
n/a
n/a
EE-PP-MM-ZZZZ
n/a
n/a
EE-PP-MM-ZZZZ
n/a
n/a
EE-PP-MM-ZZZZ
n/a
n/a
EE-PP-MM-ZZZZ
n/a
n/a
EE-PP-MM-ZZZZ
n/a
n/a
EE-PP-MM-ZZZZ
n/a
n/a
EE-PP-MM-ZZZZ
n/a
n/a
EE-PP-MM-ZZZZ
n/a
200
EE-PP-MM-ZZZZ
1
n/a
EE-PP-MM-ZZZZ
n/a
NAC Circuit 7 EE-PP-MM-ZZZZ
n/a
NAC Circuit 7 EE-PP-MM-ZZZZ
SIA– IFP-75 Panel Communicator:
Fields
SIA Event
Sent
Data
FA32000015
FA32000005
FA32010123
FA21330203
ET15110000
RP32000000
YT32980000
YT32180000
ET01440000
LB32000000
LB22000000
AT22980000 MM = 00
FT22970200
FT22970001 MM = 00
FT22980007 ZZZZ=Pt. #
FT22980007 ZZZZ=OPG #

Hide quick links: