Remote Station Applications; 1: Keltron Model 3158 Installation - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Control Panel Installation

4.15 Remote Station Applications

4.15.1 Keltron Model 3158 Installation
The control panel is compatible with Keltron Model 3158, used for a direct connection to a Keltron receiver. The 3158 reports alarms, super-
visories, and troubles. The 3158 is intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible
ratings.
Refer to the following steps to connect the 3158 to the control panel. Refer to the 3158 installation instructions for complete information.
1.
Wire the 3158 to the control panel as shown in the connection list and .Figure 4.49
2.
Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3.
Program the control panel Relay 2 for an alarm.
4.
Program the NAC circuit 2 for alarm.
5.
Program the NAC circuit 1 for supervisory non-latching
NOTE: NACs must be programmed for continuous and non-silencing
This is intended for
connection to a polarity
reversal circuit of a
remote station
receiving unit having
compatible ratings.
A 5496 must
be used for
NAC circuits
50
All circuits power-limited.
All wiring supervised.
Keltron
Receiving
Equipment
To each ground
Figure 4.49 Keltron 3158 Connection to Control Panel
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
.
Example
Model 3158
#2 not used.
Remote Station Applications
4.7K
EOL
4.7K
EOL