Operation
Silence Alarms and
Troubles
Reset Alarms
View Alarms,
Supervisories, and
Troubles
View a Points Status
Conduct a Fire Drill
Check Detector Sensitivity
Set Time and Date
Enable / Disable a Point
View Event History
For Service Call:
PNLS10165-001SK-E Rev C ECN 3220
Model IFP-75 Basic Operating Instructions
These Instructions must be framed and displayed next to the
NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the System in accordance to
NFPA 72.
Press SILENCE then enter a code if prompted. Silence LED will light.
Press RESET then enter a code if prompted.
Press up or down arrow to view Alarms, Supervisories, or Trouble
1.
Press ENTER to access Main Menu, then enter a code if prompted.
2.
Press 2 to select Point Functions.
3.
Select the module the device is located on by using the up or down arrow. Then press ENTER.
4.
Enter the point number.
1.
Press ENTER to access Main Menu, then, enter a code if prompted.
2.
Press 1 to select System Tests, then press 1 to select Fire Drill.
3.
Press ENTER to start the fire drill. Press ENTER to end the fire drill.
1.
Press ENTER to access Main Menu.
2.
Press 2 for Point Status.
3.
From the list that displays, select the SLC module where the point you want to view is located.
4.
The fourth line of the display shows the sensitivity status. "NORMAL" means the detector is in
compliance with NFPA 72. "CAL MAINT" means the detector is in compliance with NFPA 72 but
maintenance should be performed soon. "CAL TRBLE" means the detector is not in compliance
with NFPA 72.
1.
Press ENTER to access Main Menu, then enter a code if prompted.
2.
Press 4 to select Set Time & Date. Enter a code if prompted. Make changes in the fields on the
screen as necessary.
3.
Press ENTER if you want to keep the changes. Press ENTER to set the entered time and date.
1.
Rotate the key or enter a code to access to access Main Menu.
2.
Press 2 to select Point Functions.
3.
Press 1 to select Disable / Enable Point.
4.
Press 7 to Disable / Enable Pt.
5.
Use the up or down arrow to move through the list. Then press ENTER to select the module
where the point you want to disable/enable is located.
6.
Enter the point or circuit number that you want to disable/enable.
7.
Press the right arrow key to toggle between NORMAL (enable) or DISABLE.
1.
Press ENTER to access Main Menu, then enter a code if prompted.
2.
Press 3 to select event history.
3.
Press the up or down arrow to view events in the history buffer.
IFP-75
Task to Perform
panel in accordance with