Honeywell IFP-75 Installation & Operation Manual page 21

Addressable fire alarm control panel
Table of Contents

Advertisement

Calculating Current Draw and Standby Battery
5880 LED I/O Module
5883 Relay Interface
A
SK-NIC Network Interface Card
SK-FML Fiber-Optic Multi Mode
SK-FSL Fiber-Optic Single Mode
Wireless Modules
Wireless Gateway
Total System Current
2
Auxiliary Devices
IPDACT-2 IP Communicator
IPDACT-2UD IP Communicator
CELL-MOD / CELL-CAB-SK
B
Auxiliary Devices Current
Notification Appliance Circuits
5495/5499 Power Supply
C
Notification Appliances Current
D
Total current ratings of all devices in the System (line A + line B + C)
E
Total current ratings converted to amperes (line D x.001):
F
Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):
G
Multiply lines E and F.
H
Alarm sounding period in hours. (For example, 5 minutes =.0833 hours)
I
Multiply lines E and H.
3
J
Add lines G and I.
Multiply by the Derating Factor
Note 1: Total does not include isolator devices or accessory bases.
Note 2: If you use door holders, you do not need to consider the door holder current for alarm/battery standby, because the power is removed during that
time. However, during the normal operation, the door holders draw current must be included in the 2.5A total alarm current (1.0A for all other conditions)
that can be drawn from the panel.
Note 3: Use the next size battery with a capacity greater than required.
Note 4: IDP-Beam-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. This should be considered when determining
auxiliary power capacity but not calculated into current requirements for day to day operation.
power only when the test feature is used. This feature should be considered when you determine auxiliary power capacity, but are not calculated into
the current requirements for the day-to- day operation.
Note 4: The IDP-PhotoR is sold separately from the DNR. The current draw for the DNR + IDP-PhotoR is calculated by increasing the "Number of
Devices" column for each IDP-PhotoR used with a DNR.
Note 5: The DNR housing does not include a Relay circuit board. If a relay is needed, be sure to add one to the IDP-Relay & IDP-PhotoR "Number of
Devices" column for each DNR used for correct current calculations.
Note 6: The FACP can support 30 devices with LED's ON. This current draw is added to the panel's alarm current.
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Device
Table 3.3 Current Calculation Worksheet for IDP Devices (Continued)
# of
Current per Device
Devices
Standby:
Alarm:
(32 max.)
Standby:
Alarm:
(22 mA per relay)
(1 Max.)
Standby/Alarm:
(1 Max.)
Standby/Alarm:
(1 Max.)
Standby/Alarm:
Max current using external supply 40 mA
Max current SLC Power
Refer to devices manual for current rating.
Alarm:
Standby:
Alarm:
Standby:
Standby:
Alarm:
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
Refer to device manual for current rating.
24 VDC
One input circuit:
Both input circuits:
Alarm:
Alarm:
Alarm:
Total standby AH
Total alarm AH
Total ampere hours required
NOTES
Prerequisites for Installation
Standby
Current
35 mA
200 mA
0 mA
220 mA
21 mA
53 mA
79 mA
24 mA
136 mA
93 mA
155 mA
98 mA
55 mA
100 mA
mA
mA
mA
mA
15 mA
30 mA
mA
mA
mA
SK-Beam-T draws a maximum of 500mA from auxiliary
Alarm
Current
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
A
A
H
AH
H
AH
AH
x 1.25
AH
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt seriesIfp-75hv

Table of Contents