Chapter 2 Product specifications

Chapter 2 Product specifications

2.1 General specifications

The general specifications of the XGT series are as follows.
No
Item
Ambient
1
temperature
Storage
2
temperature
3
Ambient Humidity
4
Storage humidity
Vibration
5
resistance
Peak impact acceleration: 147 ㎨ (15G)
Duration : 11 ㎳,
6
Shock resistance
Pulse waveform: Half-sine (3 times for each direction of X, Y and Z)
Square wave impulse
Electrostatic discharge
7
Noise resistance
Radiation field noise
Operating
8
atmosphere
9
Altitude
10
Pollution degree
11
Cooling method
Notes
(1) IEC (International Electrotechnical Commission): An international nongovernmental organization which promotes
international cooperation in the standardization in the fields of electricity and electronics, publishes international
standards and operates relevant conformity assessment systems.
Pollution degree Pollution degree: It is an index indicating the degree of pollution of the service environment that
determines the insulation performance of a device, and pollution degree 2 indicates the state in which only non-
conductive pollution occurs. However, temporary conduction occurs in this state due to dew formation.
2-1
5~ 95%RH , (Non-condensing)
5~ 95%RH , (Non-condensing)
In case of occasional vibration
Frequency
Acceleration
5≤f< 8.4 ㎐
8.4≤f≤150 ㎐
In case of continuous vibration
Frequency
Acceleration
5≤f< 8.4 ㎐
8.4≤f≤150 ㎐
4.9m/s2 (0.5G)
noise
Category
Fast transient
/burst noise
Voltage
Free from corrosive gases and dust
Specification
0 ~ 55 C
25 ~70 70 C
Amplitude
-
3.5mm
9.8 ㎨(1G)
-
Amplitude
-
1.75mm
-
AC : ±1,500V,DC : ±900V
4.0kV (Contact discharge)
80 ~ 1000 MHz, 10V/m
Power
Digital/Analog Input/Output,
module
Communication Interface
2kV
Less than 2,000m
2 or less
Natural air cooling
Related
specifications
-
Times
X, Y, Z
IEC 61131-2
Each
direction
10 times
IEC 61131-2
Test standard of
LS ELECTRIC
IEC 61131-2
IEC 61000-4-2
IEC 61131-2,
IEC 61000-4-3
IEC 61131-2
IEC 61000-4-4
1kV

Advertisement

Table of Contents
loading

Table of Contents