Chapter 10 Emc Standard - LS ELECTRIC XGT Series User Manual

Programmable logic control ethernet module
Hide thumbs Also See for XGT Series:
Table of Contents

Advertisement

Chapter 10 EMC Standard

Chapter 10 EMC Standard
10.1 The requirements for compliance with EMC standards
The EMC Directive specifies the products must 'be so constructed that they do not cause excessive electromagnetic
interference (emissions) 'and 'are not unduly affected by electromagnetic interference (immunity)'. The applicable products
are requested to meet these requirements This section summarizes the precautions on conformance to the EMC Directive
of the machinery assembled using XGT PLC series. The details of these precautions are based on the requirements and the
applicable standards control. However, LSIS will not guarantee that the overall machinery manufactured according to the
these details conforms to the below-described directives. The method of conformance to the EMC directive and the judgment
on whether or not the machinery conforms to the EMC Directive must be determined finally by the manufacturer of the
machinery
10.1.1 EMC Standard
The standards applicable to the EMC Directive are listed below.
Specifications
Test item
EN55011
Radiated noise *2
EN50081-2
EN55011
Conducted EM
noise
EN61000-4-2
Electrostatic
immunity
EN61000-4-4
Fast transient burst
noise
EN61131-2
EN61000-4-3
Radiated field AM
modulation
EN61000-4-12
Damped oscillatory
wave immunity
*1:
QP: Quasi-peak value, Mean: Average value
* 2: The PLC is an open type device (device installed to another device) and must be installed in a conductive control panel.
The test was conducted while installed in the panel.
10-1
Test details
Electromagnetic emissions from the
product are measured
Electromagnetic emissions from the
product to the power line is measured.
Immunity test in which static electricity is
applied to the case of the equipment
Immunity test in which burst noise is
applied to the power line and signal lines
Immunity test in which field is irradiated to
the product
Immunity test in which a damped oscillatory
wave is superimposed on the power line
Standard value
30~230 ㎒ QP : 50 ㏈㎶/m *1
230~1000 ㎒ QP : 57 ㏈㎶/m
150~500 ㎑ QP :79 ㏈
Mean : 66 ㏈
500~230 ㎒ QP : 73 ㏈
Mean : 60 ㏈
15 ㎸ Aerial discharge
8 ㎸ Contact discharge
Power line: 2 ㎸
Digital /O : 1 ㎸
Analog I/O, signal lines: 1 ㎸
10Vm,26~1000 ㎒
80%AM modulation@ 1 ㎑
Power line: 1 ㎸
Digital I/O (24V or higher): 1 ㎸