E
Wiring
Use provided cable glands in order to mantain the IP protection
The current of the power supply can be limited. In order to perform this adjustment please
refer to the instruction manual.
The IEC-61851-1 ed 3 standard indicates each plug shall have protections. In case the
Charge Point has no protections inside, they shall be upstreams. It is recommended that
these protections be as follows:
°
RCD: Residual current debice. Starndards: IEC 61008-1, IEC 61009-1,IEC 60947-2 and
IEC 62423
°
Rated residual operating current not exceeding 30 mA.
RCD(s) protecting connecting points shall be at least type A.
The DC fault current shall be mesured by a RCD type B or a appropriate equipment
that ensures the disconnection of the supply in case of DC fault current above 6 mA
°
MCB: Miniature circuit breaker. Standards: IEC 60898-1 or IEC 60947-2 or IEC 61009-1
During first second shall be able to withstand 30 A
NOTE: In the following countries automatic reclosing of protection means is not allowed: DK,
UK, FR, CH.
Cable
glands M32
A
A
B
15