Master Programming Level
MS-9200UDLS PN 52750:A 11/04/05
Pressing 2 while viewing the Program Check screen will display a screen similar to the
following:
ZONES NO INPUT
05 07 09 10 11 1M001
The Zone No Input screen allows the programmer to view the zones which have not
been programmed to at least one input device (not including general alarm Zone 00).
The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have
been programmed to an addressable module (control module in this example) with an
address of 001 on loop 1 but have not been programmed to any input devices. Use the
up and down arrow keys to view all the zones without input assignments.
Pressing 3 while viewing Program Check screen will cause a screen similar to the
following to be displayed:
ZONES NO OUTPUT
05 07 09 10 11 1D001
The Zone No Output feature allows the programmer to view the zones which have not
been programmed to at least one output device (not including general alarm Zone 00).
The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have
been programmed to an addressable detector with an address of 001 on loop 1 but have
not been programmed to any output devices. Use the up and down arrow keys to view
all the zones without output assignments.
Programming
119