Programming
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
48
3.6.2 Point Program
The Point Program option allows the programmer to add a new addressable device to an
SLC loop, delete an existing device from a loop or change the programming for an
existing device. Pressing 2, while viewing Programming Screen #1, will select the
Point Program option and display the following screen:
POINT PROGRAM
1=DETECTOR
2=MODULE
Point Program Screen

3.6.2.1 Detector Programming

Pressing 1, while viewing the Point Program Screen, will allow the programmer to
add, delete or change the programming of an addressable detector. The following
screen will be displayed by the control panel:
1=ADD
2=DELETE
3=EDIT

3.6.2.1.1 Add Detector

Pressing 1 while viewing the Detector Screen will display the following screen
which allows the programmer to add a new detector address to programming:
ENTER DETECTOR#
***
A flashing cursor will appear in the position of the first asterisk to the left. The
programmer keys in the three digit detector address, such as 005.
When the last digit is keyed-in, the following screen will be displayed:
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE(ION)
Press the down arrow key to view additional choices. Press the number
corresponding to the desired selection to program that type to the newly added
detector.
SELECT TYPE
DETECTOR
Detector Screen
ADD DETECTOR
Add Detector Screen
DETECTOR TYPE
MS-9200UDLS PN 52750:A 11/04/05
Master Programming Level