Installation Location; Installation In Hazardous Areas - Emerson PACSystems RX3i IC695ECM850 Quick Start Manual

Iec-61850 ethernet communication module
Table of Contents

Advertisement

Quick Start Guide
GFK-2851A

Installation Location

2.2.
This product is intended for use with the RX3i system. Its
components are considered open equipment (having live
electrical parts that may be accessible to users) and must be
installed in an ultimate enclosure that is manufactured to provide
safety. As a minimum, the enclosure shall provide a degree of
protection against solid objects as small as 12mm (e.g. fingers).
This equates to a NEMA/UL Type 1 enclosure or an IP20 rating
(IEC60529) providing at least a pollution degree 2 environment.
For details about installing RX3i rack systems, refer to GFK-2314.
If you need technical help, contact Technical Support weblink
https://www.emerson.com/Industrial-Automation-
Controls/support.

Installation in Hazardous Areas

2.3.
The following information is for products bearing the UL marking
for Hazardous Areas or ATEX marking for explosive atmospheres:
CLASS 1 DIVISION 2 GROUPS ABCD
This equipment is an open-type device and is meant to
be installed in an enclosure suitable for the environment
that is only accessible with the use of a tool.
Hardware Installation
Chapter 2
Sep 2019
14