the Module Catalog, select the IC695ECM850 module.
Double-clicking the slot with the IC695ECM850 displays a
Settings grid where you can enter (among others) the
module's IEC 61850 network IP address, subnet mask, and
Status Address.
2.
Add IEDs and select IEC 61850 Data Objects/Data
Attributes (DO/DA): Right-click the slot with the
IC695ECM850 and select Configure IEC61850 Client to
display the integrated IEC61850 Configurator to define
and configure the IEDs with which the ECM850 will
communicate. The IEC 61850 Configurator supports both
online and offline configuration. Online, the user can
connect to the IED and browse the device's data model to
select objects of interest. Offline, the user can import an
IED Capability Description (ICD) or Configured IED
Description (CID) file preconfigured by the IED vendor to
browse and select the device's data objects. Machine
Edition automatically generates "PLC Protocol Variables"
(PPVs) from these objects for use in the ladder application.
3.
Create the RX3i application: Finally, the variables created
in the previous step are used to develop an RX3i
application program. This program, along with the
hardware configuration and network configuration is then
Status and Diagnastic Data
Chapter 3