Troubleshooting The Cisco 7507 And Cisco 7507-Mx Cooling Subsystem - Cisco 7500 Series Configuration Manual

Cisco systems bridge/router installation and configuration guide
Hide thumbs Also See for 7500 Series:
Table of Contents

Advertisement

Chapter 8
Troubleshooting a Cisco 7500 Series Router
R E V I E W D R A F T — C I S C O C O N F I D E N T I A L
If you are unable to resolve the problem or if you determine that either a power supply or a chassis
connector is faulty, contact a service representative for instructions.

Troubleshooting the Cisco 7507 and Cisco 7507-MX Cooling Subsystem

This section provides information on troubleshooting the Cisco 7507 and Cisco 7507-MX cooling
subsystem.
Check the following to help isolate the problem:
When you start up the system, does the system blower go on? To determine whether the blower is
operating, listen for the motor. In noisy environments, place your hand above and to each side of the
processor slots on the rear of the chassis (when facing the interface processor end of the router) to feel
for air being forced out the vents.
OL-5008-03 B0
If the AC power (or input power) and DC fail (or out fail) LEDs both remain off and the switch
is correctly set, suspect the power source or the power cable. Turn the switch off, connect the
power cable to another power source if available, and turn the switch back on. If the LED then
comes on, the problem is the first power source.
If the LED fails to come on after you connect the power supply to a new power source, replace
the power cord and turn the switch back on. If the AC power (or input power) LED then comes
on, return the first power cable for replacement.
If the LED still fails to come on when connected to a different power source with a new power
cable, the power supply is probably faulty. If a second power supply is available, install it in the
lower power supply bay and contact a service representative for further instructions.
On the lower power supply, is the DC fail (or out fail) LED on?
If yes, suspect the power supply. Try installing the power supply in the upper bay. If a second power
supply is present, move it to the lower bay. Turn both power supplies on to determine whether the
power supply or the power connector in the chassis is faulty; then contact a service representative
with the results.
Is the AC power (input power) LED on for the second (redundant) power supply?
If not, repeat each of the above procedures for the second power supply.
If the blower is on, the +24 VDC line to the blower is good.
If the blower is not on, there is a problem with the blower or the +24 VDC power. Ensure that the
DC fail LED is off. If the LED is off, there could be a problem with the +24 VDC supply to the
blower. See the
"Troubleshooting Blower Operation" section on page
If the blower is not on but the DC OK LED is on (which means the +24VDC power is present), the
blower connector might not be seated properly. To check the blower power connection, see the
"Removing and Replacing the Cisco 7507 and Cisco 7507-MX Blower Assembly" section on
page
6-15. Ensure that the blower connector is inserted fully in the backplane socket. After you
replace the chassis cover panel, try starting the system again.
If the following message is displayed, it indicates that the system has detected an overtemperature
condition or out-of-tolerance power inside the chassis:
Queued messages:
%ENVM-1-SHUTDOWN: Environmental Monitor initiated shutdown
If an environmental shutdown results from an out-of-tolerance power condition, the DC OK LED
will go off before the system shuts down. (See the
7507-MX Power Subsystem" section on page
Troubleshooting Guidelines for the Cisco 7507 and Cisco 7507-MX
"Troubleshooting the Cisco 7507 and Cisco
8-10.) Although an overtemperature condition is
Cisco 7500 Series Installation and Configuration Guide
8-17.
8-11