Cisco 7500 Series Configuration Manual page 106

Cisco systems bridge/router installation and configuration guide
Hide thumbs Also See for 7500 Series:
Table of Contents

Advertisement

Environmental Monitoring and Reporting Overview for the Cisco 7500 Series
In the following example, all current measured values fall within the Normal status range. The first
voltage parameter in the table, +12(V), shows that the Normal range for the +12V sense spans 10.20V
through 13.80V. The current measured value, 12.05V, falls within that range and is therefore displayed
in the Normal column.
Router# show env table
Environmental Statistics
Environmental status as of Wed 5-10-1995 18:50:21
Data is 46 second(s) old, refresh in 14 second(s)
WARNING: Fan has reached CRITICAL level
Voltage Parameters:
SENSE
-------|--------------------|------------------------|------------------
+12(V)
+5(V)
-12(V)
+24(V)
Temperature Parameters:
SENSE
------|-------------|------------|-------------|--------------|---------
Inlet
Air-flow
The following example shows only the Temperature Parameters section of the table. In this example, the
measured value at the inlet sensor is 41°C, which falls within the warning range (39°C through 46°C)
and is therefore displayed in the Warning column.
Temperature Parameters:
SENSE
------|-------------|------------|-------------|--------------|-----
Inlet
Air-flow
In the Cisco 7505, the show environment all command displays an extended report that includes all the
information in the show environment command display, plus the power supply status, the number of
intermittent power failures (if any) since the system was last powered on, and the measured values at the
temperature sensors and the DC lines. The refresh time indicates that the parameters will be measured
again in 29 seconds; any changes to a measurement will not be reflected in the display until at least 40
seconds have elapsed and the current information is refreshed.
Router# show env all
Environmental Statistics
Environmental status as of Wed 5-10-1995 19:10:41
Data is 31 second(s) old, refresh in 29 second(s)
WARNING: Fan has reached CRITICAL level
Power Supply: 600W AC (or 600W DC)
No Intermittent Powerfails
+12 volts measured at
+5 volts measured at
-12 volts measured at -12.05(V)
Cisco 7500 Series Installation and Configuration Guide
2-28
CRITICAL
10.20
4.74
-10.20
20.00
WARNING
NORMAL
10
32(C)
10
40(C)
WARNING
NORMAL
10
10
40(C)
12.00(V)
5.02(V)
NORMAL
12.05(V)
13.80
4.96(V)
5.26
-12.05(V)
-13.80
23.80(V)
28.00
WARNING
CRITICAL SHUTDOWN
39
46
70
77
WARNING
CRITICAL SHUTDOWN
39
41(C)
46
70
77
Chapter 2
Preparing for Installation
CRITICAL
64
88
64
88
OL-5008-03 B0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750775137505

Table of Contents