Magnetek IMPULSE G+ Mini Technical Manual page 60

Hide thumbs Also See for IMPULSE G+ Mini:
Table of Contents

Advertisement

5.1.3.8
LOC/REM Run Select
If the run reference/speed reference are switched between serial mode and terminal mode, B03.07 determines
action after the switch.
Parameter
B03.07
LOC/REM Run Sel
00 Cycle Extrn Run
01 Accept Extrn RUN
B03.10
Allow Run at Power UP
00 Disabled
01 Enabled
Parameter
B03.15
Reference Source 2 Selection
00 Keypad
01 Terminals
02 Modbus Communication
03 Option PCB
04 Pulse Input
B03.16
Run Source 2 Selection
00 Keypad
01 Terminals
02 Modbus Communication
03 Option PCB
Name
Determines action after switching Run/Speed
reference source.
If the run command is present at the time when
Run/Speed reference source is switched, it
requires the run command to be removed and then
reapplied from the new source to resume the
normal operation.
If the run command is present at the time when the
Run/Speed reference source is switched, it does
not require the run command from the new source
to be removed. The normal operation will continue.
Determines whether a run command, enabled on
VFD power up, will run the motor. When disabled,
a new run command is required before the motor
will run.
Name
Selects frequency reference source when
H01.xx = 1F.
Keypad
Control circuit terminal
Modbus Serial Communication
Industrial Communication
Pulse Input (Terminal RP)
Selects run command source when H01.xx = 1F.
Keypad
Control circuit terminal
Modbus Serial Communication
Industrial Communication
Function
Function
IMPULSE
Range
Default
00–01
00
00–01
00
Range
Default
00–04
01
00–03
01
®
•G+ Mini Technical Manual
November 2020
Page 60