Magnetek IMPULSE G+ Mini Technical Manual page 136

Hide thumbs Also See for IMPULSE G+ Mini:
Table of Contents

Advertisement

Fault
CPF02
A/D Conversion Error. An A/D conversion error
occurred.
CPF03
PWM Data Error. There is a problem with the
PWM data.
CPF06
EEPROM Data Error. There is an error in the
data saved to EEPROM.
CPF07
Terminal Board Communications Error. A
communication error occurred at the terminal
board.
CPF08
EEPROM Serial Communications Fault.
EEPROM communications are not functioning
properly.
CPF11
RAM Fault.
CPF12
FLASH Memory Fault. Problem with the ROM
(FLASH memory).
CPF13
Watchdog Circuit Exception. Control circuit
damage.
CPF14
Control Circuit Fault. CPU Error (CPU operates
incorrectly due to noise, etc.)
CPF16
Clock Fault. Standard clock error.
CPF17
Timing Fault. A timing error occurred during an
internal process.
CPF18 and
Control Circuit Fault. CPU error (CPU operates
incorrectly due to noise, etc).
CPF19
CPF20 and
RAM fault, FLASH memory error, watchdog
circuit exception.
CPF21
CPF22
A/D Conversion Fault. A/D conversion error.
CPF23
PWM Feedback Fault. PWM feedback error.
CPF24
VFD Capacity Signal Fault. Entered a capacity
that does not exist (checked when the VFD is
powered up).
CRST
Cannot reset. External fault occurred and reset
button was pressed before motor was completely
stopped.
Fault reset was being executed when a RUN
command is executed during a fault.
Fault or Indicator Name/Description
Corrective Action
1.
Cycle power to the VFD.
2.
Ensure that the control board terminals and
wiring are shielded from electrical noise.
3.
Check resistance of potentiometer.
4.
Replace the VFD.
1.
Cycle power to the VFD.
2.
Replace the control board.
1.
Cycle power to the VFD.
2.
If the problem continues, replace the VFD.
1.
Cycle power to the VFD.
2.
Check connections on the control board.
1.
Cycle power to the VFD.
2.
If the problem continues, replace the VFD.
1.
Cycle power to the VFD.
2.
Replace the VFD.
1.
Cycle power to the VFD.
2.
Replace the VFD.
1.
Cycle power to the VFD.
2.
Replace the VFD.
1.
Cycle power to the VFD.
2.
Replace the VFD.
1.
Cycle power to the VFD.
2.
Replace the VFD.
1.
Cycle power to the VFD.
2.
Replace the VFD.
1.
Cycle power to the VFD.
2.
Ensure that the control board terminals and
wiring are shielded from electrical noise.
3.
Replace the VFD.
1.
Cycle power to the VFD.
2.
Replace the VFD.
1.
Cycle power to the VFD.
2.
Ensure that the control board terminals and
wiring are shielded from electrical noise.
3.
Check resistance of potentiometer.
1.
Cycle power to the VFD.
2.
Replace the VFD.
1.
Cycle power to the VFD.
2.
Replace the VFD.
1.
Wait for motor to come to complete stop.
2.
Reset fault before issuing a RUN command.
IMPULSE
®
•G+ Mini Technical Manual
November 2020
Page 136