ETC Sohrana Dual Tech Installation Manual page 12

Dimming sensor 0-10 v
Table of Contents

Advertisement

ETC Installation Guide
0–10 V Dimming Switch Sensor
Power Up
Apply power to the sensor and lighting loads, and allow the sensor to fully
calibrate. During power up, a green LED will blink. Once the sensor is
calibrated and ready for testing and use, the sensor LEDs will indicate in blue
with each motion sensed and green with each sound detected (HFD sensor)
within the sensor's configured range.
Note:
occupancy is detected for 10 minutes, the connected load will be
switched Off. The delay time can be set to 10 seconds for testing
convenience by setting the Time rotary switch to position 1. See
on
page 10. If the sensor has been reconfigured from its factory
default operational settings (see
operate as expected in Test mode.
Test
1. Move around the space to verify that occupancy is detected as expected in
the space. Remove any obstacles that obstruct effective sensing.
2. Move outside of the desired range and test if the HFD sensor can detect
sound. The green LED will indicate with each detection. Change the
sensitivity level as needed to either increase or decrease sensitivity of the
HFD sensor in the space.
3. When testing is complete, return the Time rotary switch back to the
desired delay time and set the Lux rotary switch to the desired value for
your installation. See
4. Install the wall plate to the station.
0–10 V Dimming Switch Sensor
By factory default, once power is applied to the sensor and no
Lux on page 10
DIP Switch
Settings), the sensor will
for details.
Page 12 of 12