Rotary Switches - ETC Sohrana Dual Tech Installation Manual

Dimming sensor 0-10 v
Table of Contents

Advertisement

ETC Installation Guide
0–10 V Dimming Switch Sensor

Rotary Switches

Use the rotary switches behind the push-button cover to set the sensor delay
time and ambient light level (Lux) threshold for Light Sensing. Change these
settings according to your installation requirements.
Position
Lux
Time
(min)
*Default settings.
† Test mode, which sets the timer to 10 seconds.
Lux
The Lux setting determines the ambient light level (threshold) when the
sensor will inhibit switching on the lighting load. If the light level is at or
above the set threshold, the lighting load will not turn on. By default, this
setting is 24 hours, which disables Light Sensing for testing and
commissioning purposes. Set to the desired value for your installation.
Time
Time setting determines the delay time (in minutes) that the sensor will hold
the lighting load on after occupancy was last detected. By default, this setting
is 10 minutes.