ETC Sohrana Dual Tech Installation Manual page 11

Dimming sensor 0-10 v
Table of Contents

Advertisement

ETC Installation Guide
0–10 V Dimming Switch Sensor
Use the Buttons
Use the buttons to change the state of the connected load,
either On or Off, or to manually fade the level of the lighting
between 20–100%. You can also use the buttons to configure
the preferred level of the lighting for an occupancy event. By default, the set
level is 100%.
Change State
Press and release either button to turn the lights On or Off according to the
sensor configuration and the sensor's current state.
Note:
Off), and the Lux rotary switch is at any position other than position 7
(disabled), pressing either button will not turn the lighting On if the
ambient light level is higher than the Lux threshold.
Manual Dimming Mode
Press and hold a button to place the sensor in manual dimming mode. While
in dimming mode you can use the buttons in the following ways:
Press and hold the left button to lower the lighting level to the lowest
level (20%). The sensor LED will indicate in Blue when the level is at its
lowest level.
Press and hold the right button to raise the lighting level to the highest
level (100%). The sensor LED will indicate in Green when the level is at
its highest level.
Press and release either button to increment the lighting level while in
manual dimming mode.
Set the Occupancy Level
1. Press and hold either button to place the sensor in manual dimming
mode.
2. Press and release either button to increment the lighting to the desired
level.
3. Press and hold both buttons simultaneously until the sensor LED
indicates in steady Blue.
4. Release both buttons. The LED will blink for ten seconds and the lighting
load will flash On and Off twice to indicate that the new level is saved.
0–10 V Dimming Switch Sensor
If the sensor is configured as a vacancy sensor (DIP Switch 4
Page 11 of 12