(2) Acceleration feed forward
Vibration may occur at 10 to 20 Hz during acceleration/deceleration when a short time constant of
30 ms or less is applied, and a position loop gain (PGN1) higher than the general standard value or
SHG control is used. This is because the torque is insufficient when starting or when starting
deceleration, and can be resolved by setting the acceleration feed forward gain (SV015 (FFC)).
This is also effective in reducing the peak current (torque).
While measuring the current command waveform, increase FFC by 50 to 100 at a time and set the
value where vibration does not occur.
Current
command
(%)
Acceleration feed forward gain means that the speed loop gain during acceleration/deceleration is
raised equivalently. Thus, the torque (current command) required during acceleration/deceleration
starts sooner. The synchronization precision will improve if the FFC of the delayed side axis is
raised between axes for which high-precision synchronous control (such as synchronous tapping
control and superimposition control).
No.
Abbrev.
SV015
FFC
Downloaded from
ManualsNet.com
200
100
0
0
20
Time (ms)
No FFC setting
Parameter name
When a relative error in the synchronous control is large, apply this
Acceleration rate
parameter to the axis that is delaying. The standard setting value is "0".
feed forward gain
For the SHG control, set to "100".
To adjust a relative error in acceleration/deceleration, increase the value
by 50 to 100 at a time.
Overshooting occurs easily when a value above the standard value is set during
POINT
SHG control.
search engine
9. Adjustment
40
60
80
100
Explanation
9 - 27
200
100
0
0
20
40
Time (ms)
With FFC setting
60
80
100
Setting range
0 to 999
(%)