Fig. 27 Connection El4712 - Beckhoff EL47 Series Documentation

Analog output terminal with oversampling
Table of Contents

Advertisement

Connection EL4712
Fig. 27: Connection EL4712
Terminal point
Name
No.
+ Output 1
1
+24 V
2
0 V
3
Shield
4
+ Output 2
5
+24 V
6
0 V
7
Shield
8
EL47xx
Description
+ Output 1
+24 V (internally connected to terminal point 6 and positive power contact)
0 V (internally connected to terminal point  7 and negative power contact)
Shield (internally connected to terminal point 8)
+ Output 2
+24 V (internally connected to terminal point 2 and positive power contact)
0 V (internally connected to terminal point  3 and negative power contact)
Shield (internally connected to terminal point 4)