Read I-7530A-Mr Can Filter Configuration; Testing The I-7530A-Mr Module - ICP DAS USA I-7530A-MR-G User Manual

Rtu to can
Table of Contents

Advertisement

3.3.3

Read I-7530A-MR CAN Filter Configuration

Click the "Read from Module" item on the Utility tool bar to read CAN
filter setting from the I-7530A-MR module and save the CAN filter setting
as a file (*.FLT).
Figure 3-22 Read CAN filter form the I-7530A-MR module

Testing the I-7530A-MR module

3.4
The following procedure will guide users to learn how to
transmit/receive CAN messages to/from other devices/PCs by using the I-
7530A-MR converter.
1. Set the Init/Normal switch to the Normal position, which is found on the
back of the I-7530A-MR module.
2. Connect the I-7530A-MR's CAN port into the CAN network, which must
at least have one CAN device on the network.
3. Supply the 10~30 V
power terminal.
4. The PWR LED on the I-7530A-MR module will be turned on and the
other LEDs will be turned off. That means the I-7530A-MR is working in
the operation mode.
5. Run the UART2CAN Utility software after connecting the PC and the I-
7530A-MR via cable CA-0910. Please refer to the figure 2-14.
6. Select the PC COM port, baud rate and data format, which will be used
to connect with the COM port of the I-7530A-MR.
I-7530A-MR Modbus RTU to CAN Converter User's Manual (Version 1.08, 07/2019) ------------- 36