3. SPECIFICATION
Measurement Specification
Continuity (to IEC61557-4)
Open Circuit
Short Circuit
Voltage(DC)
Current
Greater than
Greater than 4V
200mA
Operating range(as in IEC61557) 20Ωrange:0.2Ω〜19.99Ω/200ΩRange:20Ω〜199.9Ω
Insulation Resistance (to IEC61557-2)
Open Circuit
Rated Current
Voltage (DC)
1mA or greater
500V +20%−0%
@ 500kΩ
Operating range(as in IEC61557) 20MΩ Range:0.5MΩ〜19.99MΩ/200MΩ Range:20MΩ〜100MΩ
Loop Impedance (to IEC61557-3)
Nominal Test
Rated Voltage
Current at 0Ω
(AC)
External Loop
25A/10ms
230V+10%-15%
50Hz
15mA/350ms max.
Operating range(as in IEC61557) 20Ω Range:2Ω〜19.99Ω/2000Ω Range:100Ω〜1999Ω
RCD testing (to IEC61557-6)
Rated Voltage
Function
(AC)
RCD × 1/2
230V+10%-15%
RCD × 1
50Hz
FAST
Voltage Measurement
Rated Voltage
100〜250V 50Hz
GlobalTestSupply
www.
Range
20/200Ω
Auto-Ranging
Up to 2Ω
Over 2Ω
Range
20/200MΩ
Auto-Ranging
Range
20Ω
2000Ω
Trip Current
Trip Current
Settings
Duration
10/30/100/300/
2000ms
500mA
150mA
50ms
Measuring Range
100〜250V 50Hz
— 6 —
Accuracy
±(3%rdg+4dgt)
±(3%rdg+3dgt)
Accuracy
±(3% rdg +3dgt)
Accuracy
±(3%rdg +8dgt)
±(3%rdg +8dgt)
Accuracy
Trip Current:
-8% 〜-2%
Trip Time
±(1%rdg+3dgt)
Trip Current:
+2% 〜+8%
Accuracy
3%rdg
.com
sales@GlobalTestSupply.com

Advertisement

Table of Contents
loading