3. SPECIFICATION

Continuity (to IEC61557-4)
Open Circuit
Voltage(DC)
Greater than 4V
Operating range(as in IEC61557) 20Ωrange:0.2Ω∼19.99Ω/200ΩRange:20Ω∼199.9Ω
Insulation Resistance (to IEC61557-2)
Open Circuit
Voltage (DC)
500V +20%−0%
Operating range(as in IEC61557) 20MΩ Range:0.5MΩ∼19.99MΩ/200MΩ Range:20MΩ∼100MΩ
Loop Impedance (to IEC61557-3)
Rated Voltage
(AC)
230V+10%−15%
50Hz
Operating range(as in IEC61557) 20Ω Range:2Ω∼19.99Ω/2000Ω Range:100Ω∼1999Ω
RCD testing (to IEC61557-6)
Rated Voltage
Function
RCD × 1/2
230V+10%−15%
RCD × 1
FAST
Voltage Measurement
Rated Voltage
100∼250V 50Hz
Measurement Specification
Short Circuit
Current
Greater than
200mA
Rated Current
1mA or greater
@ 500kΩ
Nominal Test
Current at 0Ω
External Loop
25A/10ms
15mA/350ms max.
Trip Current
(AC)
Settings
10/30/100/300/
500mA
50Hz
150mA
Measuring Range
100∼250V 50Hz
Range
20/200Ω
Auto-Ranging
Up to 2Ω
Over 2Ω
Range
20/200MΩ
Auto-Ranging
Range
20Ω
2000Ω
Trip Current
Duration
2000ms
50ms
― 6 ―
Accuracy
±(3%rdg+4dgt)
±(3%rdg+3dgt)
Accuracy
±(3% rdg +3dgt)
Accuracy
±(3%rdg +8dgt)
±(3%rdg +8dgt)
Accuracy
Trip Current:
−8% ∼−2%
Trip Time
±(1%rdg+3dgt)
Trip Current:
+2% ∼+8%
Accuracy
3%rdg