Gas Connection - AGA Professional AMPRO36DF-SS User Manual

90 dual fuel
Table of Contents

Advertisement

Check the appliance is electrically safe and gas sound when you have finished.
Fig. 8.25
2.5" (6.5 cm)
ArtNo.280-0073 - Wall behind the range
Area approx 17" (431 mm) x 5¾" (146 mm)
Fig. 8.26
ArtNo280-0074 Connection fron Rear
Fig. 8.27
ArtNo.280-0075 - Opening inside the drawer
10¼" (26 cm)
8¾" (22.2 cm) from
the side of the range
16" (41 cm)
Area accessible through the drawer
cavity with the drawer removed.
7¾" (19.7 cm)
6" (15.2 cm) from the oor
with range at lowest point
INSTALLATION

Gas Connection

Installation of this range MUST conform with local codes
or, in the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1-latest edition.
In Canada
The range MUST be installed in accordance with the current
CGA Standard CAN/CGA-B149 – Installation Codes for Gas
Burning Appliances and Equipment and/or local codes.
In The Commonwealth Of Massachusetts
When installed within the Commonwealth of Massachusetts
this product MUST be installed by a licensed plumber or gas
fitter.
A 'T' handle type manual gas valve MUST be installed in the
gas supply line to this appliance.
Gas Supply Requirements
The recommended gas pipe outlet locations are shown in
Fig. 8.25, Fig. 8.26 and Fig. 8.27.
Provide Adequate Gas Supply
Before installation, ensure that the local distribution
conditions (nature of the gas and gas pressure) and the
adjustment of the appliance are compatible.
The range is designed to operate at a manifold pressure of 4''
of water column (1 kPa) on natural gas. A conversion kit for
LP gas (Propane) is supplied with the range. When converted
to LP gas, a pressure of 10'' of water column (2.49 kPa) is
required.
Make sure you are supplying your range with the
n
n
correct type of gas.
If the range is to be used on LP gas a qualified LP installer
MUST convert it. We recommend that the range be converted
before installation. This must be done before the range can
be used on LP gas.
For proper operation the pressure of natural gas supplied to
the regulator must be between 4½'' and 13'' of water column
(1.12-3.24 kPa).
For LP gas, the pressure supplied must be between 10'' and
13'' of water column (2.49-3.24 kPa).
When checking for proper operation of the regulator, the
inlet pressure must be at least 1'' (0.25 kPa) greater than the
operating (manifold) pressure as given above.
The pressure regulator located at the inlet of the range
manifold must remain in the supply line regardless of
whether natural or LP gas is being used.
A flexible metal appliance connector used to connect the
range to the gas supply line should have an I.D. of ½'' and be
5' in length for ease of installation.
34