UPS Specifications

Unit (Capacity)
general
topology
Certifications
input Characteristics
input Voltage
1
input Frequency
input Capacity
input /(max input) Current @208V
input/(max. input) Current @240V
input power Factor
Current tHd (linear load)
internal AC input breaker rating
battery Characteristics
battery type
backup time, fully charged @ 0.7
power factor, 77 °F
backup time, fully charged @ 0.85
power factor, 77 °F
recharge time
battery Voltage (nominal)
output Characteristics
output Voltage
output Voltage regulation
output Frequency
AUto/mAn Frequency
Voltage tHd
Common-mode noise
rated load power Factor
1
Efficiency (ac-dc-ac)
Voltage transient
Voltage transient recovery
rated output Current (rms)
max peak output Current
inverter overload Capacity
bypass overload Capacity
Crest Factor
1.
Input/output figures rated for 240 volts unless otherwise stated.
when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.
battery
backup time may vary depending on the operating conditions and ambient temperature at the installation site.
3.
An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
1600Xp Series installation and operation manual
STANDARD MODEL: 3.6 – 10 KVA
3.6kVA (3.1 kW)
6 kVA (5.1 kW)
1
AnSi C62.41 (ieee 587), Ul 1778, CUl, Ce, FCC Class A , neC (nFpS-70), nemA/
pe1-1993, oSHA, ASme, iSo 9001, iSo 14001:2004 , roHS Compliant
Single-phase, 208/240 Vac, +10% to -30%
3.6 kVA
6 kVA
17.9 (18.7) A
29.8 (31.1) A
15.5 (16.2) A
25.9 (27.0) A
0.98 typical, 0.95 minimum@ 100% load
< 5% total harmonic distortion
30 A/277 V
50 A/277 V
Valve regulated lead Acid, Flame retardant
8 min.
8 min.
2
7 min.
7 min.
2
24 hr. (full), 12 hr. (90%) for internal batteries only
144 Vdc
216 Vdc
Single-phase, 240/208/120 V
±0.5 Hz/1.0 Hz/1.5 Hz (factory or authorized service center selectable only)
Factory or authorized service center selectable only
< 3% for linear load; < 6% for non-linear load
>83%
50 ms to within 2% of nominal
15 A
45 A
125% for 30 sec./150% for 10 sec.
125% for 10 min./1000% for 1 cycle
8 kVA (6.8 kW)
1
true on-line
45 – 65 Hz (auto-sensing)
8.0 kVA
38.9 (40.5) A
33.7 (35.1) A
60 A/277 V
7 min.
2
2
7 min.
2
2
= ± 3%
< 0.5 Vrms
0.85 (0.6 – 1.0) lagging
< ±8% (load of 0 – 100 %)
25 A
33.3 A
75 A
100 A
3.0
Output ratings given for 0.85PF are only valid
10 kVA (8.5 kW)
1
1
1
10 kVA
48.6 (50.2) A
42.1 (43.5) A
63 A/277 V
7 min.
2
5 min.
2
3
288 Vdc
>85%
41.6 A
125 A
19