Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP Installation And Operation Manual page 53

Single phase - 3.6/6/8/10/14/18/22 kva
Hide thumbs Also See for UNINTERRUPTIBLE POWER SYSTEM 1600XP:
Table of Contents

Advertisement

Recalibrate the Touchscreen
the touchscreen on the UpS is shipped from the factory already calibrated. However, at some point the
touchscreen calibration may need to be refreshed so that the active portion of the screen matches the
underlying graphics.
recalibrate the touchscreen as follows:
1.
press the
Settings tab.
2.
press the
Disp/Reye key.
3.
page forward to the second page and press the line:
810
Cali Display
4.
the settings display will show the Cali display screen.
5.
press the
Enable key.
6.
press the
Write key. (this will write the subsequent calibration val-
ues to the Control board.)
7.
the display will switch to the C
8.
Gently press a stylus, or similar fine pointed tool, to the center of the
X located at the top left-hand side of the display.
9.
As soon as the information is read, a second X will be displayed at
the top right-hand of the display. repeat Step 7.
10.
repeat Step 7 for X displayed at the lower right-hand side of the
display.
11.
repeat Step 7 for the X displayed at the lower left-hand side of the
display.
12.
After completing Step 10, the display will return to the
screen. press the Quit key.
the touchscreen has been successfully recalibrated and the resulting
values stored on the Control pCb.
1600Xp Series installation and operation manual
AlibrAtion SCreen shown below.
Cali Display
inV
12:35 pm
HOME
USR
Main
Monitor
Settings
Records
810 Cali Display
Disabled
Quit
208V
Enable
240V
Write
4GHI
5JKL
6MNO
7PQRS
8TUV
9WXYZ
0-:
Shift
on-line
Cali display SCreen
CAlibrAtion SCreen
45