Operating the UPS

the 1600Xp should be installed and adjusted by an operator. once installed, the 1600Xp is designed
to be operated by laymen. Anyone not familiar with this UpS should read the manual before attempting
to operate it.

Initial Startup (First Power-Up)

The first time the UPS is activated after being shipped from the factory, an initialization program will
require the operator to input the following parameters. input rated Voltage, output rated Voltage, UpS
date, and UpS time. the UpS display operation is explained in detail on pages 32-59.
the input frequency defaults to 60 Hz.
The first screen displayed during the initial startup sequence requires the operator to select the nominal
input Voltage. Select from 208V, 230V, or 240V, and press the Write key.
if the command has been accepted, the word "Successful" will appear at the bottom left side of the
display.
1.
repeat the process in step 1 in selecting the rated output Voltage.
2.
Use the keypad to type in the current date in the format:
3.
Use the keypad to type in the current time in 12 hour format:
4.
the main screen is now displayed. Verify the UpS is in bypASS mode. the mode (lower right side
of the display) should display Bypass. if it does not display Bypass, press and momentarily hold
the STOP button on the main display.
5.
with the UpS in bypass mode, cycle power to the UpS as follows:
At the rear of the UpS switch the main circuit breaker mCCb to oFF.
leave the UpS off until the dC bus is safely discharged (approximately 5-10 minutes).
restart the UpS by switching the main circuit breaker on.
the table below summarizes the initialization parameters:
ID
Command
111
rated Vin
215
rated Vout
634
UpS date
635
UpS time
1600Xp Series installation and operation manual
Select from 208V, 230V, or 240V, and press Write.
Select from 208V, 230V, or 240V, and press Write.
input the date in this format: Mon 10/05/2009. and press Write.
input the current time in 12 hour format: 12:15 PM and press Write.
Mon 10/05/2009. and press Write.
12:15 PM and press Write.