Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP Installation And Operation Manual page 30

Single phase - 3.6/6/8/10/14/18/22 kva
Hide thumbs Also See for UNINTERRUPTIBLE POWER SYSTEM 1600XP:
Table of Contents

Advertisement

Capacity
general
topology
Certifications
input Characteristics
input Voltage
1
input Frequency
input Capacity
input /(max input) Current @208V
input /(max input) Current @240V
input power Factor
Current tHd (linear load)
internal AC input breaker rating
battery Characteristics
battery type
backup time, fully charged @ 0.7
power factor, 77 F
backup time, fully charged @ 0.85
power factor, 77 F
recharge time
battery Voltage (nominal)
output Characteristics
output Voltage
output Voltage regulation
output Frequency
AUto/mAn Frequency
Voltage tHd
Common-mode noise
rated load power Factor
1
Efficiency (AC-DC-AC)
Voltage transient
Voltage transient recovery
rated output Current (rms)
max peak output Current
inverter overload Capacity
bypass overload Capacity
Crest Factor
1.
Input/output figures rated for 240 volts unless otherwise stated.
when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.
battery
backup time may vary depending on the operating conditions and ambient temperature at the installation site.
3.
An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
4.
Subject to update without notice.
5.
derate to 18.7 kVA (15.9 kw) for 50 Hz operation.
22
STANDARD MODELS: 14 – 22 KVA
14 kVA (11.9 kW)
1
AnSi C62.41 (ieee 587), Ul 1778, CUl, Ce, FCC Class A , neC (nFpS-70),
nemA/pe1-1993, oSHA, ASme, iSo 9001, iSo 14001:2004 , roHS Compliant
Single-phase, 208/240 VAC, +10% to –30%
45-65 Hz (auto-sensing)
14 kVA
67.2 (68.9) A
58.2 (59.7) A
0.98 typical, 0.95 minimum@ 100% load
100 A / 277 V
Valve regulated lead Acid, Flame retardant
7 min.
2
7 min.
2
24hr. (full), 12hr.(90%) for internal batteries only
Single-phase, 240/208/120 volts
±0.5Hz/1.0Hz/1.5Hz (factory/authorized service center selectable only)
Factory or authorized service center selectable only
< 3% for linear load; < 6% for non-linear load
0.85 (0.6 - 1.0) lagging
< ±8% (load of 0 to 100 %)
50 ms to within 2% of nominal
58 A
174 A
125%-30 sec./150%-10 sec
125%-10 min./1000%-1 cycle
18 kVA (15.3 kW)
22 kVA (18.7 kW)
1
true on-line
18 kVA
86.4 (88.1) A
74.9 (76.3) A
< 5%
5 min.
2
288 VdC
= ±3%
< .5 Vrms
>86%
4
75 A
225 A
3.0
Output ratings given for 0.85PF are only valid
1600Xp Series installation and operation manual
1, 5
1
1
22 kVA
106 (107) A
92.0 (93.0) A
1
125 A / 277 V
5 min.
2
3 min.
2
3
91.6 A
275 A

Advertisement