Saving Of Parameter Settings - B+B Sensors DM-Compact Series Operating Manual

Table of Contents

Advertisement

OPEARTING MANUAL
After you have modified the head code a reset is necessary to activate the change. [►6 Operating]
To switch to the ASCII protocol you can use also the following command:
Decimal:
131
HEX:
0x83
Data, Answer:
byte 1
Result:
0 – Binary-Protocol
1 – ASCII-Protocol
7.2.4

Saving of parameter settings

After power on of the DM sensor the flash mode is active. It means, changed parameter settings will be saved in the DM-internal Flash-EEPROM
and will be kept also after the sensor is switched off.
In case settings should be changed quite often or continuously the flash mode can be switched off by using the following command:
Decimal:
112
HEX:
0x70
Data, Answer:
byte 1
Result:
0 – Data will not be written in the Flash
1 – Data will be written in the Flash
If the flash mode is deactivated, all settings will only be kept as long as the unit is powered. If the unit is switched off and powered on again all
previous settings are lost. The command 0x71 will poll the current status.
You will find a detailed protocol and command description on the software package in the directory: \Commands.