ELECTRICAL INSTALLATION
Grid Connection
Observations
• The short-circuit current at the connection point cannot exceed 10 kA.
• The impedance of the loop with respect to ground must not exceed 80 Ω.
• This connection must be protected, in a previous phase (main electrical panel where the
supply comes from), by a four-pole magnetothermic switch (moulded case), minimum of
100 A; type curve D, by a differential switch capable of withstanding at least the maximum
current of the previously mentioned switch, with a sensitivity of 300 mA; type A.
• The overvoltage protection of 20% Vn (Nominal Voltage) will be necessary.
• The dimensions of the wiring must comply with the regulations
and standards in force in the country of installation.
• To calculate the minimum section, remember that the fast
charger has a maximum primary winding current of 130 A.
38

FINAL MECHANICAL PREPARATION

Final Steps

Material
Assembly
Part
Size
Structure
Foot Cover Front
N/A
Structure
Foot Cover Back
N/A
Structure
Internal Screws
M5 x10
ISO 7380-2
Structure
External Screws
M6 x12
ISO 7380-2
Top Cover
Eye-Bolt DIN 580
M12
Top Cover
Top Cover Screws
M12 x16
Top Cover
Washers
M12
Quantity
Tools Recommended
1
N/A
1
N/A
7
Allen for M5 Screws
6
Torx for M6 rounded
2
Socket wrench for M12
2
Socket wrench for M12
2
N/A
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents