Parameter
23 LEgI
ESC
MODE
24 CLOC
ESC
MODE
26 tSFt
ESC
MODE
Description
Enabling the anti-legionella function
for boilers with domestic hot water tank
(available with OTBus connection between
the WiFi Box and the boiler or the RF receiv -
er and the boiler or the Hi, Comfort T100
and the boiler, if provided for by the OTBus
protocol). Default set to OFF .
Value settable to ON or OFF . If this param -
eter is set to ON, every 20 cycles of DHW
request, a request is activated for boiler
top-up with DHW delivery setpoint of 60°C
at the time 01.00 on the next day.
If the 20 cycles are not reached within one
week, a request is activated for boiler top-
up with DHW delivery setpoint of 60°C at
the time 01.00 on the seventh day
Enabling domestic hot water timer for
boilers with domestic hot water tank
(available with OTBus connection be -
tween the WiFi Box and the boiler or
the RF receiver and the boiler or the
Hi, Comfort T100 and the boiler, if provid -
ed for by the OTBus protocol).
Default set to OFF .
This value can be set to ON or OFF .
Setting this parameter to ON, the domes -
tic hot water time periods can be pro -
grammed, as explained in "3.8 Setting the
DHW time program" to page 54.
The parameter will only be shown if the
SEnS parameter is OFF (available with
OTBus connection between the WiFi Box
and the boiler or the RF receiver and
the boiler or the
the boiler, if provided for by the OTBus
protocol). Default set to 10°C. The value
can be set from 1°C to 20°C. The value
set for this parameter will be subtract -
ed from the heating delivery setpoint
calculated by the
only in AUTO
during the T2 (economy) or T1 (an -
ti-freeze) time period.
69