Variable output relay card LC32 (optional - 043011X0)
The variable output relay LC32 consists of a small card with a switchover of free contacts (closed means contact bet-
ween C and NO). Operation is managed by the software.
For installation, carefully follow the instructions provided in the kit package and on the wiring diagram of fig. 70.
To use the desired function, refer to the table 3.
Table 3- Settings LC32
Parameter b07
Function LC32
0
Manages a secondary gas valve (default)
1
Use as an alarm output (warning light comes on)
2
Manages a water loading valve
3
Manages a solar 3-way valve
4
Manages a second heating pump
5
Use as an alarm output (warning light goes off)
6
Indicates ignition of the burner
7
Manages the trap heater
ON/OFF (A fig. 31) configuration
Table 4- Switch A setting
DHW configuration
Parameter b06
b06=0
b06=1
b06=2
b01 = 3
b06=3
b06=4

2.6 Fume ducts

B
THE BOILERS MUST BE INSTALLED IN ROOMS THAT MEET THE FUNDA-
MENTAL VENTILATION REQUIREMENTS. OTHERWISE THERE IS A DAN-
GER OF ASPHYXIA OR POISONING.
READ THE INSTALLATION AND MAINTENANCE INSTRUCTIONS BEFORE
INSTALLING THE UNIT.
ALSO RESPECT THE DESIGN INSTRUCTIONS.
IN CASE OF PRESSURES EXCEEDING 200 Pa INSIDE THE FUME EXHAUST
PIPES, THE USE OF CLASS "H1" FLUES IS MANDATORY.
Important
The unit is a "C-type" with sealed chamber and forced draft; the air inlet and fume outlet must be connected to one of
the extraction/suction systems indicated below. Before proceeding with installation, check and carefully observe the
above instructions. Also, comply with the provisions on the positioning of wall and/or roof terminals and the minimum
distances from windows, walls, ventilation openings, etc.
In case of installation with maximum resistance (coaxial or separate flue) it is advisable to carry out a calibra-
tion procedure [AUTO SETUP] to optimize boiler combustion.
24
BlueHelix HiTech RRT C
Contact open disables DHW and re-enables it if closed.
Contact open disables heating and displays F50. Contact closed enables heating.
The contact acts as a room thermostat.
Contact open displays F51 and the boiler continues to operate.
It is used as an alarm.
The contact acts as a limit thermostat, if open it displays F53 and turns off the request.
cod. 3541V691 - Rev. 00 - 04/2022
Action LC32
The contacts are closed when the gas valve (in the boiler)
is powered
The contacts are closed when there is an error condition
(generic)
The contacts are closed until the water pressure in the hea-
ting circuit is restored to the normal level (after manual or
automatic topping up)
The contacts are closed when the DHW mode is active
The contacts are closed when the heating mode is active
The contacts are opened when there is an error condition
(generic)
The contacts are closed when the flame is present
The contacts are closed when the frost protection mode is
active