Ferroli BlueHelix HiTech RRT C Instructions For Use, Installation & Maintenance page 47

Table of Contents

Advertisement

BlueHelix HiTech RRT C
Fault code
Fault
Exchanger protection
A09
intervention
Overtemperature protec-
F09
tion intervention
F10
Flow sensor fault
A11
Gas valve connection
F11
Return sensor fault
F12
DHW sensor fault
F13
Fume probe fault
Fume extraction duct
A14
safety device intervention
F15 - A07
High fume temperature
F19
Card parameter fault
System pressure slightly
F21
high (visible only in the
Alarm menu)
A23-A24-F51
Pressure sensor fault
Intervention of fault F40
A26
more than 3 times in 24
hours
EN
Possible cause
No water circulation in the
system
Poor circulation and ano-
malous flow probe tempera-
ture increase
blocked exchanger
Flow sensor damaged
No water circulation in the
system
Air in the system
Sensor damaged
Wiring shorted
Wiring disconnected
Gas valve connector not
inserted.
Electrical connection bet-
ween control unit and gas
valve interrupted.
Gas valve damaged.
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Probe damaged
Wiring shorted
Wiring disconnected
Fault A07 generated 3
times in the last 24 hours
The fume probe detects an
excessive temperature
Wrong card parameter set-
ting
System water pressure too
high
Wrongly configured para-
meter
System pressure problems
(transducer)
b06 set to 3
System water pressure too
high
Expansion vessel dischar-
ged or damaged
cod. 3541V691 - Rev. 00 - 04/2022
Cure
Check the circulating pump and heating
system
Vent the system
check the exchanger and system
Check correct positioning and operation
of the flow sensor and replace it if neces-
sary
Check the circulating pump and heating
system
Vent the system
Check the wiring or replace the sensor
Insert the connector
Check the wiring
Replace the gas valve
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the fume
probe
See fault A07
Check the exchanger
Check the fume probe
Check the flue material parameter
Check and if necessary modify parameter
b15 to 3
Partially drain the system to a pressure
(shown on the display) of 1÷1.5 bar.
Check the expansion tank
Check if the parameter b04 is correctly
configured
System pressure value outside set limits
(transducer)
Partially drain the system to a pressure
(shown on the display) of 1÷1.5 bar
Charge or replace the expansion vessel
47