Calibration procedure [AUTO SETUP]
1. Access the parameters menu[TSP].
2. Select parameter b27 with the
ting buttons and set it to 5 with the
DHW buttons.
Confirm with the button
Return to the main menu[MENU].
3. Return to the installer menu [Service] >enter the
Password 1234 (see fig. 17).
Now the menu for calibration[Auto Setup] is
also displayed.
4. Select it and confirm with the button
5. The procedure starts automatically finding the op-
timal ignition point (a few ignition attempts are re-
quired to determine the exact point).
6. After ignition, the burner goes to heating at the va-
rious powers (max, med, min) indicated by point
a
(fig. 41).
If the system heat dissipation is not sufficient to
end the procedure, a DHW request can be activa-
ted only after the burner has ignited.
7. At the end of the calibration sequence [Comple-
ted] will be displayed for a few seconds and then
return to the Service menu.
8. If the ignition sequence described in point "6" is
not successful, the message max_err at point
and an error code at point
9. Exit with the button
Repeat the sequence from point "1".
The calibration procedure [Auto Setup] can only be performed if parameter b27 is set to 5.
Parameter b27 can be set manually to the value 5, or by:
changing the parameter "gas type" b03.
setting parameter P67 to 1.
changing the value of parameter P68.
doing "Restore Factory Values" with the parameter b29=10 (after carrying out this operation, disconnect and re-
connect the power supply for about ten seconds).
In each of the above cases, b27 automatically changes to 5.
It is necessary to perform the calibration procedure [Auto Setup] in the following cases:
after replacing the PCB
after changing the gas (b03)
setting parameter P67 to 1
after changing the value of parameter P68
after setting parameter b27 to 5 for replacement of components such as the electrode, burner, gas valve, fan or for
installations with maximum flue resistance
in case of fault conditions A01, A06 or other faults when required (see table 11. Respect the sequence of fault
cures).
The calibration procedure [Auto Setup] resets the combustion parameters previously recorded and must be done
only in the cases described above.
32
and
hea-
and
.
.
a
c
will appear (fig. 41).
and unlock the boiler.
cod. 3541V691 - Rev. 00 - 04/2022
BlueHelix HiTech RRT C
AUTO SETUP
Step:
Power:
CH temp:
Alarm:
fig. 41
a
max ...
-- %
22°
c
none
EN