DNP V3.00 Device Profile
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Name
60
50-1 picked up
61
51 picked up
62
CLP OFF
63
CLP BLOCKED
64
CLP running
65
Dyn set. ACTIVE
66
PhA InrushBlk
67
PhB InrushBlk
68
PhC InrushBlk
69
INRUSH X-BLK
70
50-1 InRushPU
71
50N-1 InRushPU
72
51 InRushPU
73
51N InRushPU
74
67-1 InRushPU
75
67N-1 InRushPU
76
67-TOC
InRushPU
77
67N-TOC
InRushPU
78
Gnd InRush PU
79
Ia InRush PU
80
Ib InRush PU
81
Ic InRush PU
82
InRush OFF
InRushPhBLOCK
83
ED
84
InRush Gnd BLK
85
>BLOCK 67-1
86
>BLOCK 67-TOC
87
>BLOCK 67N-1
3-8
50-1 picked up; ON = 1, OFF = 0
51 picked up; ON = 1, OFF = 0
Cold-Load-Pickup switched OFF; ON = 1, OFF = 0
Cold-Load-Pickup is BLOCKED; Blocked = 1, Unblocked = 0
Cold-Load-Pickup is RUNNING; ON = 1, OFF = 0
Dynamic settings are ACTIVE; ON = 1, OFF = 0

InRush Function

Phase A trip blocked by inrush detection; ON = 1, OFF = 0
Phase B trip blocked by inrush detection; ON = 1, OFF = 0
Phase C trip blocked by inrush detection; ON = 1, OFF = 0
Cross blk: PhX blocked Phy; ON = 1, OFF = 0
50-1 InRush picked up; ON = 1, OFF = 0
50N-1 InRush picked up; ON = 1, OFF = 0
51 InRush picked up; ON = 1, OFF = 0
51N InRush picked up; ON = 1, OFF = 0
67-1 InRush picked up; ON = 1, OFF = 0
67N-1 InRush picked up; ON = 1, OFF = 0
67-TOC InRush picked up; ON = 1, OFF = 0
67N-TOC InRush picked up; ON = 1, OFF = 0
Ground InRush picked up; ON = 1, OFF = 0
Phase A InRush picked up; ON = 1, OFF = 0
Phase B InRush picked up; ON = 1, OFF = 0
Phase C InRush picked up; ON = 1, OFF = 0
InRush OFF; ON = 1, OFF = 0
InRush Phase BLOCKED; ON = 1, OFF = 0
InRush Ground BLOCKED; ON = 1, OFF = 0

Directional time overcurrent protection

>BLOCK 67-1; ON = 1, OFF = 0
>BLOCK 67-TOC; ON = 1, OFF = 0
>BLOCK 67N-1; ON = 1, OFF = 0
Description
7SJ61/62/63 6MD63 DNP3.0 Device Profile Document
1810
3
1820
3
1994
3
1995
3
1996
3
1997
3
1840
3
1841
3
1842
3
1843
3
7551
3
7552
3
7553
3
7554
3
7559
3
7560
3
7561
3
7562
3
7564
3
7565
3
7566
3
7567
3
7556
3
7557
3
7558
3
2621
3
2622
3
2623
3
C53000-L1840-A001-01

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec4 7sj62Siprotec4 7sj63Siprotec4 6md63

Table of Contents