Binary Output Status Points
Object Number: 10
Request Function Codes supported: 1 (Read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks/Binary Output Status
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate),
Point
Index
Name
18
auto-
recl.ac.
19
Protection
20
Reset
LEDs
21
Group A
22
Group B
23
Group C
24
Group D
25
ModeREM
OTE
26
Output 1
27
Output 2
28
Output 3
29
Output 4
30
Output 5
31
Output 6
32
Output 7
33
Output 8
34
Output 9
35
Output 10
7SJ61/62/63 6MD63 DNP3.0 Device Profile Document
C53000-L1840-A001-01
6 (direct operate, no ack)
Description
Internal commands
activation of Auto-reclosure function
Protection activation
Reset LEDs
Select parametergroup A and deactivate
parametergroup B,C,D
Select parametergroup B and deactivate
parametergroup A,C,D
Select parametergroup C and deactivate
parametergroup A,B,D
Select parametergroup D and deactivate
parametergroup A,B,C
Mode remote control; Latch On = the device is
switch in an unlocked mode for one unlocked
switching only. After that unlocked switching or
after a time-out time of 5 minutes the device will
be switched in the locked position automatically.
If parametrized the "actual-value comparison" will
be always active. If the "Control authority mode"
is switched to local mode, the "Mode remote
control" command latch on is without any impact.
Output channel (user defined single
point output commands)
Output channel 1
Output channel 2
Output channel 3
Output channel 4
Output channel 5
Output channel 6
Output channel 7
Output channel 8
Output channel 9
Output channel 10
DNP V3.00 Device Profile
Supported Control
Relay Output Block
Object
Fields
Latch On, Latch
Off
Latch On, Latch
Off
Latch On
Latch On
Latch On
Latch On
Latch On
Latch On; Latch
Off
Latch On, Latch
Off, Pulse On
Latch On, Latch
Off, Pulse On
Latch On, Latch
Off, Pulse On
Latch On, Latch
Off, Pulse On
Latch On, Latch
Off, Pulse On
Latch On, Latch
Off, Pulse On
Latch On, Latch
Off, Pulse On
Latch On, Latch
Off, Pulse On
Latch On, Latch
Off, Pulse On
Latch On, Latch
Off, Pulse On
Int.
No.
60
3-21