Overview - Siemens SIPROTEC4 7SJ61 Manual

Communication module
Hide thumbs Also See for SIPROTEC4 7SJ61:
Table of Contents

Advertisement

1

Overview

Overview
Mapping:
7SJ61/62/63 6MD63 DNP3.0 Device Profile Document
C53000-L1840-A001-01
This document describes the DNP standard mapping for SIPROTEC4
devices.
Standard mapping one specifies the analog values for the voltage
range of 32.767 kV and two DNP index points for double point
commands.
Standard mapping two specifies the analog values for the voltage
range of 327.67 kV and two DNP index points for double point
commands.
Standard mapping three specifies the analog values for the voltage
range of 32.767 kV and one DNP index point for double point
commands.
Standard mapping four specifies the analog values for the voltage
range of 327.67 kV and one DNP index point for double point
commands.
The following functions, described within the instruction book of
the 7SJ61/62/63 and 6MD63 for some protocols, are not available
via DNP 3.00.
Function
Oscillographic wave form
capture
Remote settings
Additional information points
Additional control
command/devices (Be careful:
Don't delete or rename the
predefined control devices. The
user can not recreate control
command/devices after deleting
or renaming them within the
matrix)
Time synchronization
Block Data Transmission
Generate Indications
Remedy
Redundant service port via modem
or direct connection for DIGSI 4
Redundant service port via modem
or direct connection for DIGSI 4
map "User defined channels" via
CFC
If accidentally deleted or renamed,
do not save the setting changes or
create a new device within the DIGSI
manager. You must reprogram the
entire relay after creating a new
device.
Use IRIG B input
None
None
1
1-1