11.4.1 Operation test run

11.4.2 Actuator test run

EKHWET90~120BAV3
R32 Split series – Domestic hot water tank
4P680077-1 – 2021.11
To perform an actuator test run.
Purpose
Perform test runs on the unit and monitor the tank temperature to check if the
unit is working correctly. The following test run should be made:
Tank
To perform an operation test run
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Tank operation.
To monitor tank temperatures
During test run, the correct operation of the unit can be checked by monitoring its
tank temperature (domestic hot water mode).
To monitor the temperatures:
1 In the menu, go to Sensors.
2 Select the temperature information.
1 Set the user permission level to Installer. See
the user permission
2 Go to [A.1]: Commissioning > Operation test run.
3 Select the Tank..
4 Select OK to confirm.
Result: The test run starts. It stops automatically when ready
(±30 min).
To stop the test run manually:
1 In the menu, go to Stop test run.
2 Select OK to confirm.
INFORMATION
If the outdoor temperature is outside the range of operation, the unit may NOT
operate or may NOT deliver the required capacity.
Purpose
Perform an actuator test run to confirm the operation of the different actuators.
For example, when you select Booster heater, a test run of the booster heater
will start.
To perform an actuator test run
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Tank operation.
1 Set the user permission level to Installer. See
user permission
level" [
4
level" [
 52].
4
 52].
11
Commissioning
|
"To change
"To change the
Installer reference guide