Field settings table
Breadcrumb
Field code
Setting name
9.5.1
[4-06]
Emergency
└─ Power consumption control
9.9.1
[4-08]
Power consumption control
9.9.2
[4-09]
Type
9.9.3
[5-05]
Limit
9.9.8
[5-09]
Limit
9.9.D
[4-01]
Priority heater
└─ Sensors
9.B.3
[1-0A]
Averaging time
Installer settings
9.E
[3-00]
Auto restart
9.F
[E-08]
Power saving function
9.G
Disable protections
└─ Overview field settings
9.I
[0-0B]
Setting temperature water value for high ambient temp. for DHW WD curve.
9.I
[0-0C]
Setting temperature water value for low ambient temp. for DHW WD curve.
9.I
[0-0D]
High ambient temp. for DHW WD curve.
9.I
[0-0E]
Low ambient temp. for DHW WD curve.
9.I
[1-0A]
What is the averaging time for the outdoor temp?
9.I
[2-00]
When should the disinfection function be executed?
9.I
[2-01]
Should the disinfection function be executed?
9.I
[2-02]
When should the disinfection function start?
9.I
[2-03]
What is the disinfection target temperature?
9.I
[2-04]
How long must the tank temperature be maintained?
9.I
[3-00]
Is auto restart of the unit allowed?
9.I
[4-01]
Which electric heater has priority?
9.I
[4-03]
Operation permission of the booster heater.
9.I
[4-06]
Emergency
9.I
[4-08]
Which power limitation mode is required on the system?
9.I
[4-09]
Which power limitation type is required?
9.I
[5-05]
What is the requested limit for DI1?
9.I
[5-09]
What is the requested limit for DI1?
9.I
[6-00]
The temperature difference determining the heat pump ON temperature.
9.I
[6-01]
The temperature difference determining the heat pump OFF temperature.
9.I
[6-02]
What is the capacity of the booster heater?
9.I
[6-08]
What is the hysteresis to be used in reheat mode?
9.I
[6-0A]
What is the desired comfort storage temperature?
9.I
[6-0B]
What is the desired eco storage temperature?
9.I
[6-0C]
What is the desired reheat temperature?
9.I
[6-0D]
What is the desired DHW production type?
9.I
[6-0E]
What is the maximum DHW temperature setpoint?
Range, step
Default value
R/W
0: Manual
1: Automatic
R/W
0: No limitation
1: Continuous
R/W
0: Current
1: Power
R/W
12~50 A, step: 1 A
12 A
R/W
3~20 kW, step: 0,5 kW
3 kW
R/O
0: None
1: BSH
2: BUH
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
0: No
1: Yes
R/W
0: Disabled
1: Enabled
R/W
0: No
1: Yes
R/W
35~[6-0E]°C, step: 1°C
43°C
R/W
45~[6-0E]°C, step: 1°C
50°C
R/W
10~25°C, step: 1°C
25°C
R/W
-40~5°C, step: 1°C
-15°C
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0: No
1: Yes
R/W
0~23 hour, step: 1 hour
1
R/W
55~max(55, 6-0E), step: 1°C
70°C
R/W
5~60 min, step: 5 min
10 min
R/W
0: No
1: Yes
R/O
0: None
1: BSH
2: BUH
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
R/W
0: Manual
1: Automatic
R/W
0: No limitation
1: Continuous
R/W
0: Current
1: Power
R/W
12~50 A, step: 1 A
12 A
R/W
3~20 kW, step: 0,5 kW
3 kW
R/W
2~20°C, step: 1°C
6°C
R/W
0~10°C, step: 1°C
2°C
R/W
0~10kW, step: 0,2kW
1.2kW
R/W
2~20°C, step: 1°C
10°C
R/W
30~[6-0E]°C, step: 1°C
50°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
40~75°C, step: 1°C
75°C
3/4
Installer setting at variance with
default value
Date