6.5.1 About checking the refrigerant piping ......16 6.5.2 Precautions when checking the refrigerant piping ..16 6.5.3 To check for leaks............16 6.5.4 To perform vacuum drying .......... 16 Installer reference guide 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 Split series 4P600463-2 – 2019.10...
(on top of the ▪ The installation of the system, and all activities described in the instructions described in the Daikin documentation). installation manual and in the installer reference guide MUST be performed by an authorised installer.
Page 4
▪ Joints made in installation between parts of refrigerant system shall be accessible for maintenance purposes. WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. Installation space requirements NOTICE ▪...
▪ Charge the refrigerant in liquid form. Adding it in gas form may prevent normal operation. ▪ Toxic gas may be produced if refrigerant gas comes into contact with fire. 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B Installer reference guide R32 Split series 4P600463-2 – 2019.10...
Depending on the radio waves, a distance of disconnection, having a contact separation in all poles 1 metre may not be sufficient. providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring. Installer reference guide 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 Split series 4P600463-2 – 2019.10...
Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B Installer reference guide R32 Split series 4P600463-2 –...
▪ Install units, power cables and communication wiring at least 3 m away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 3 m may not be sufficient. Installer reference guide 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 Split series 4P600463-2 – 2019.10...
▪ Where the voltage fluctuates a lot Allow 300 mm of work space below the ceiling surface and 250 mm ▪ In vehicles or vessels for piping and electrical servicing. ▪ Where acidic or alkaline vapour is present 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B Installer reference guide R32 Split series 4P600463-2 – 2019.10...
Depending on the applicable legislation and the unit's maximum working pressure (see "PS High" on the unit Snow cover or shed name plate), larger piping thickness might be required. Pedestal Installer reference guide 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 Split series 4P600463-2 – 2019.10...
▪ Make electrical connections to the fixed wiring. ▪ All components procured on-site and all electrical 6.2.2 To open the outdoor unit construction MUST comply with applicable legislation. DANGER: RISK OF ELECTROCUTION DANGER: RISK OF BURNING 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B Installer reference guide R32 Split series 4P600463-2 – 2019.10...
(see the following figure). NOTICE If the unit is installed in a cold climate, take adequate measures so that the evacuated condensate CANNOT freeze. Installer reference guide 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 Split series 4P600463-2 – 2019.10...
▪ Protect the piping as described in the following table to prevent dirt, liquid or dust from entering the piping. ▪ Use caution when passing copper tubes through walls (see figure below). 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B Installer reference guide R32 Split series 4P600463-2 – 2019.10...
▪ The stop valves are factory closed. ▪ The following figure shows the stop valve parts required when ▪ After handling the stop valve, tighten the stem cap, and check for handling the valve. refrigerant leaks. 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B Installer reference guide R32 Split series 4P600463-2 – 2019.10...
If there is a possibility of moisture being present in the refrigerant piping (for example, water may have entered the piping), first carry out the vacuum drying procedure below until all moisture has been removed. Installer reference guide 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 Split series 4P600463-2 – 2019.10...
Refrigerant type: R32 Charging refrigerant Global warming potential (GWP) value: 675 6.6.1 About charging refrigerant The outdoor unit is factory charged with refrigerant, but in some cases the following might be necessary: 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B Installer reference guide R32 Split series 4P600463-2 – 2019.10...
(see unit name Before connecting the electrical wiring plate) + the determined additional amount. Make sure: ▪ The refrigerant piping is connected and checked ▪ The water piping is connected Installer reference guide 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 Split series 4P600463-2 – 2019.10...
The X NOT allowed voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram. 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B Installer reference guide R32 Split series 4P600463-2 – 2019.10...
Liquid pipe Liquid pipe insulation 4 Make sure to connect correct wiring to correct room (A to A, B Finishing tape to B). 2 Install the service cover. Installer reference guide 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 Split series 4P600463-2 – 2019.10...
The standby electricity saving function is turned off before shipping. To turn on standby electricity saving function Prerequisite: The main power supply MUST be turned off. 1 Remove the service cover. 2 Disconnect the selective standby electricity saving connector. 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B Installer reference guide R32 Split series 4P600463-2 – 2019.10...
Make sure drainage flows smoothly. commissioning instructions in this chapter, a general Possible consequence: Condensate water might drip. commissioning checklist is also available on the Daikin Business Portal (authentication required). The indoor unit receives the signals of the user interface.
2 Measure the temperature at the indoor unit inlet and outlet after maintenance/inspection checklist is also available on the running the unit for about 20 minutes. The difference should be Daikin Business Portal (authentication required). more than 8°C (cooling) or 15°C (heating). general...
Disposing of the system typically consists of the following stages: Pumping down the system. Bringing the system to a specialized treatment facility. INFORMATION For more details, see the service manual. Installer reference guide 2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 Split series 4P600463-2 – 2019.10...
Self-combustion and explosion of the compressor because of air going into the operating compressor. ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). ▪ Use a separate recovery system so that the unit's compressor does NOT have to operate.
Authorised installer the accompanying documentation. Technical skilled person who is qualified to install the Field supply product. Equipment NOT made by Daikin that can be combined with User product according instructions Person who is owner of the product and/or operates the accompanying documentation.