Daikin R32 Split Series Installer's Reference Manual page 114

Domestic hot water tank
Hide thumbs Also See for R32 Split Series:
Table of Contents

Advertisement

2/4
Field settings table
Breadcrumb
Field code
Setting name
Tank
5.2
[6-0A]
Comfort setpoint
5.3
[6-0B]
Eco setpoint
5.4
[6-0C]
Reheat setpoint
5.6
[6-0D]
Heat up mode
└─ Disinfection
5.7.1
[2-01]
Activation
5.7.2
[2-00]
Operation day
5.7.3
[2-02]
Start time
5.7.4
[2-03]
Tank setpoint
5.7.5
[2-04]
Duration
Tank
5.8
[6-0E]
Maximum
5.9
[6-00]
Hysteresis
5.A
[6-08]
Hysteresis
5.B
Setpoint mode
└─ WD curve
5.C
[0-0B]
Setting temperature water value for high ambient temp. for DHW WD curve.
5.C
[0-0C]
Setting temperature water value for low ambient temp. for DHW WD curve.
5.C
[0-0D]
High ambient temp. for DHW WD curve.
5.C
[0-0E]
Low ambient temp. for DHW WD curve.
Tank
5.D
[6-01]
Margin
5.F
[A-00]
Priority schedule
5.G
[A-01]
Operation mode
5.H
[8-03]
Quick mode timer
User settings
└─ Quiet
7.4.1
Mode
7.4.3
Level
Installer settings
└─ Configuration wizard
└─ System
9.1.3.3
[E-05]
Domestic hot water
[E-06]
[E-07]
9.1.3.4
[4-06]
Emergency
9.1.3.7
[6-02]
BSH capacity
└─ Tank
9.1.B.1
[6-0D]
Heat up mode
9.1.B.2
[6-0A]
Comfort setpoint
9.1.B.3
[6-0B]
Eco setpoint
9.1.B.4
[6-0C]
Reheat setpoint
9.1.B.6
[6-08]
Reheat hysteresis
└─ Booster heater
9.4.1
[6-02]
Capacity
9.4.3
[8-03]
Quick mode timer
9.4.4
[4-03]
Operation
└─ Emergency
4P688157-1 - 2021.11
Range, step
Default value
R/W
30~[6-0E]°C, step: 1°C
50°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
0: No
1: Yes
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0~23 hour, step: 1 hour
1
R/W
55-max(55, 6-0E)~75°C, step: 1°C
70°C
R/W
5~60 min, step: 5 min
10 min
R/W
40~75°C, step: 1°C
75°C
R/W
2~20°C, step: 1°C
6°C
R/W
2~20°C, step: 1°C
10°C
R/W
0: Fixed
1: Weather dependent
R/W
35~[6-0E]°C, step: 1°C
43°C
R/W
45~[6-0E]°C, step: 1°C
50°C
R/W
10~25°C, step: 1°C
25°C
R/W
-40~5°C, step: 1°C
-15°C
R/W
0~10°C, step: 1°C
2°C
R/W
0: DHW
1: Air Conditioning
R/W
0: Efficient
1: Quick
R/W
Turbo: 10 min
Normal: 20 min
Economic: 30 min
R/W
0: OFF
1: Manual
2: Automatic
R/W
0: Quiet
1: More Quiet
2: Most Quiet
R/O
Integrated
R/W
0: Manual
1: Automatic
R/W
0~10kW, step: 0,2kW
1.2kW
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
30~[6-0E]°C, step: 1°C
50°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
2~20°C, step: 1°C
10°C
R/W
0~10kW, step: 0,2kW
1.2kW
R/W
5~95 min, step: 5 min
20 min
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off