Do you have a question about the R32 Split Series and is the answer not in the manual?
Questions and answers
sanjeev chawla
March 24, 2025
What is the nitrogen pressure recommended in dain r-32 split ac to find the leakges
1 comments:
Mr. Anderson
March 24, 2025
The recommended nitrogen pressure for leak detection in Daikin R32 Split Series air conditioners is at least 200 kPa (2 bar). However, it is recommended to pressurize to 3000 kPa (30 bar) to detect small leaks.
The original documentation is written in English. All other languages are translations. Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required).
Indicates a situation that could result in equipment or property damage. INFORMATION Indicates useful tips or additional information. Symbols used on the unit: ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin. WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
Instructions for equipment using R32 refrigerant WARNING: MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 8
WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. WARNING If one or more rooms are connected to the unit using a duct system, make sure: ▪...
Page 9
1.8≤x<2.2 m Wall-mounted units ≥2.2 m Ceiling-mounted units 3 Use the graph or table to determine the minimum floor area. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 10
59.9 7.956 m Total refrigerant charge in the system Minimum floor area (a) Ceiling-mounted unit (= Ceiling-mounted unit) ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
▪ When the refrigerant system is to be opened, refrigerant MUST be treated according to the applicable legislation. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
MUST be installed in the fixed wiring. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 14
▪ Make sure all covers are closed before starting up the unit. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 15
Running the product in reversed phase can break the compressor and other parts. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Site made joints directly connecting piping to indoor units shall be of non permanent type. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 17
675. Do NOT vent these gases into the atmosphere. ▪ When charging refrigerant, ALWAYS use protective gloves and safety glasses. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 18
Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 19
Working on an indoor unit while performing a test operation is dangerous. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 20
Do NOT touch the compressor with bare hands. "15 Troubleshooting" [ 64]) Troubleshooting (see DANGER: RISK OF ELECTROCUTION DANGER: RISK OF BURNING/SCALDING ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 21
▪ Even when the LEDs are off, the terminal block and the PCB may be powered. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
At least 2 persons MUST handle the box with the unit. 4.2 Outdoor unit 4.2.1 To unpack the outdoor unit ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models. 5.2.1 Identification label: Outdoor unit Location ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Otherwise condensation on the unit or refrigerant pipes, air filter dirt or drain blockage may cause dripping, and objects under the unit may get dirty or damaged. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 28
If the outdoor unit is exposed to direct sea winds, install a windbreaker. ▪ Height of windbreaker≥1.5×height of outdoor unit ▪ Mind the service space requirements when installing the windbreaker. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
NOT affected by the snow. If necessary, install a snow cover or shed and a pedestal. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
NOTICE When closing the outdoor unit cover, make sure that the tightening torque does NOT exceed 1.3 N•m. 3× ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Fix the unit securely by means of foundation bolts in accordance with the foundation drawing. Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field supply). ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
1 Prepare 2 cables as indicated in the following illustration (field supply). 2 Place the 2 cables over the outdoor unit. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 34
(field supply). 4 Attach the ends of the cables. 5 Tighten the cables. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Depending on the applicable legislation and the maximum working pressure of the unit (see "PS High" on the unit name plate), larger piping thickness might be required. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
675. Do NOT vent these gases into the atmosphere. ▪ When charging refrigerant, ALWAYS use protective gloves and safety glasses. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material may dissolve and damage the system. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
ALWAYS use a spanner and torque wrench together to tighten the flare nut when connecting the piping. This to prevent nut cracking and leaks. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Clutch type Wing nut type (Ridgid-type) (Imperial-type) 0~0.5 mm 1.0~1.5 mm 1.5~2.0 mm 5 Check that the flaring is properly made. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
1 Connect the liquid refrigerant connection from the indoor unit to the liquid stop valve of the outdoor unit. Liquid stop valve ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Make sure that the gas stop valve and liquid stop valve are firmly closed before performing the leak test or vacuum drying. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
If the pressure… Then… Does not change There is no moisture in the system. This procedure is finished. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 44
NOT present any problem for correct operation of the unit. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
WARNING NEVER directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
675. Do NOT vent these gases into the atmosphere. ▪ When charging refrigerant, ALWAYS use protective gloves and safety glasses. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
2 Fix the label on the inside of the outdoor unit near the gas and liquid stop valves. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Also read the precautions and requirements in the "2 General safety precautions" [ 5]. INFORMATION Also read "9.1.3 Specifications of standard wiring components" [ 52]. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Page 50
All electrical parts (including thermistors) are powered by the power supply. Do not touch them with bare hands. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
NOTICE When closing the outdoor unit cover, make sure that the tightening torque does NOT exceed 1.3 N•m. 3× ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
The power supply voltage matches the voltage on the identification label of the unit. There are NO loose connections or damaged electrical components in the switch box. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
▪ When the power turns back on after a power break, the previously selected mode will be resumed. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
12.5 Starting up the outdoor unit See the indoor unit installation manual for configuration and commissioning of the system. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Do NOT rinse the unit. This may cause electric shocks or fire. 14.3 Checklist for yearly maintenance of the outdoor unit Check the following at least once a year: ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Use approved refrigerants and lubricants only. DANGER: RISK OF BURNING/SCALDING Do NOT touch the compressor with bare hands. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
15.3.1 Symptom: Indoor units fall, vibrate or make noise Possible causes Corrective action The indoor units are not installed Install the indoor units securely. securely ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
▪ Even when the LEDs are off, the terminal block and the PCB may be powered. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
4 Check on the manifold if the vacuum is reached. 5 After 2-3 minutes, close the gas stop valve and stop forced cooling. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Warm the outside temperature thermistor on the outdoor unit to ≥−10°C. Result: Operation will start. ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B + Installer reference guide RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-9J – 2020.05...
Technical data 17 Technical data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). 17.1 Wiring diagram The wiring diagram is delivered with the unit, located inside of the outdoor unit (bottom side of the top plate).
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Page 76
4P513661-9J 2020.05 Verantwortung für Energie und Umwelt...
Need help?
Do you have a question about the R32 Split Series and is the answer not in the manual?
Questions and answers
What is the nitrogen pressure recommended in dain r-32 split ac to find the leakges
The recommended nitrogen pressure for leak detection in Daikin R32 Split Series air conditioners is at least 200 kPa (2 bar). However, it is recommended to pressurize to 3000 kPa (30 bar) to detect small leaks.
This answer is automatically generated