Watts AERCO EXT Installation, Operation & Maintenance Manual page 81

Modulex ufly controller & bcm
Table of Contents

Advertisement

Ufly Controller and BCM for Modulex EXT
0 APPENDIX B: BMM PARAMETERS
PARAMETER
DESCRIPTION
Burner: soft shutdown - NOT
646
APPLICABLE.
Note: Leave at default value of 0
Fan: pulse/revolution
527
Note: Leave at the default value of 2
486
Fan regulation: proportional band
487
Fan regulation: integral gain
489
Fan: PWM min.
337
Modulation Gradient
526
Fan: Maximum Speed
319
Maximum Modulation
Minimum modulation
346
(Burner Minimum modulation level)
314
Standby modulation
620
Postpurge: fan speed
617
Ignition: minimum modulation
618
Ignition: maximum modulation
353
Temperature control: proportional band
354
Temperature control: integral gain
478
Temperature control: derivative gain
34
Burner Hysteresis
336
Temperature control: slope limit
OMM-0159_A • 6/28/2022
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
ENTRY RANGE
DEFAULT
0
0/1-4
2
MLX EXT 450 2S
-1100 2S: 10
0-50
MLX EXT 1500 2S
-3000 2S: 30
0-50
9
5-15%
8%
1-100%
2%
MLX EXT 450 2S
-1100 2S: 90Hz
50-120Hz
MLX EXT 1500 2S
-3000 2S: 91Hz
1-100%
100%
MLX EXT 450 2S
-1100 2S: 34%
1-100%
MLX EXT 1500 2S
-3000 2S: 31%
MLX EXT 450 2S
-1100 2S: 31%
0-100%
MLX EXT 1500 2S
-3000 2S: 33%
MLX EXT 450 2S
-1100 2S: 31%
0-100%
MLX EXT 1500 2S
-3000 2S: 33%
0-100%
32%
0-100%
82%
0°F to 90°F
(0°C to 50°C)
45°F (25C)
Units may be expressed
in R or K
0-50
12
0-50
0
9°F to 36°F
(5°C to 20°C)
9°F (5°C)
Units may be expressed
in R or K
0°F to 54°F/min
18°F/min
(0°C to 30°C/min)
(10°C/min)